Fire-Lite Alarms H355 Installation And Maintenance Instructions Download Page 2

offer maximum performance when tested and maintained in compliance with 
NFPA 72.

A.  Test Magnet (p/n M02-04-01 or M02-09-00)

 

1.   Place the optional test magnet against the cover in the magnet test 

area, as shown in Figure 3, to activate the test feature.

 

2.   The LEDs should latch on within 10 seconds, indicating alarm and 

annunciating the panel.

 

3. Reset the detector at the system control panel.

B.  Direct Heat Method (Hair dryer of 1000 – 1500 watts)
 

1.  From the side of the detector, direct the heat toward the sensor. Hold 

the heat source about 6 inches (15 cm) away to prevent damage to the 
cover during testing.

 

2.  The LEDs on the detector should light when the temperature at the 

detector reaches the alarm set point. If the LEDs fail to light, check the 
power to the detector and the wiring in the detector base.

 

3. Reset the detector at the system control panel.

Detectors  that  fail  these  tests  should  be  cleaned  as  described  under  MAIN-
TENANCE and retested. If the detectors still fail these tests, they should be 
returned for repair.

FL-400-001 

I56-3657-002R 

 

 

©2008 Fire-Lite 

FCC STATEMENT

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must 
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide 
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used 
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try 
to correct the interference by one or more of the following measures:
 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

Please refer to insert for the Limitations of Fire Alarm Systems

FIGURE 3. VIEWS SHOWING POSITION OF TEST MAGNET:

LED

TEST MAGNET 

MARKER

LED

TEST

MAGNET 

MARKER

C0152-00

MAINTENANCE

NOTE: Before cleaning notify the proper authorities that the system is under-
going maintenance, and therefore the system will temporarily be out of ser-
vice. Disable the loop or system undergoing maintenance to prevent unwanted 
alarms.

It  is  recommended  that  the  sensor  be  removed  from  its  mounting  base  for 
easier cleaning and that sensors be cleaned at least once a year. Use a vacuum 
cleaner to remove dust from the sensing chamber.

FIGURE 4:

C0151-00