Fire-Lite Alarms CP350 Installation And Maintenance Instructions Download Page 2

TESTING

Detectors must be tested after installation and following periodic mainte-
nance. However, before testing, notify the proper authorities that the
smoke detector system is undergoing maintenance and the system will
be temporarily out of service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
Test the sensors as follows:
A. Test Magnet (P/N M02-04-01 or M02-09-00)

1. Test  the sensor by positioning the optional test magnet against the

sensor plastic in the magnet test area, as shown in Figure 3.

2. Two LEDs on the sensor are controlled by the panel to indicate sen-

sor status. Coded signals, transmitted from the panel, can cause the
LEDs to blink, latch on, or latch off. Refer to the control panel techni-
cal documentation for sensor LED operation and expected delay to
alarm.

B. Smoke Entry: Aerosol Generator (Gemini 501)

The  GEMINI  model 501 aerosol generator can be used  for  smoke
entry testing. Set the generator to represent 4%/ft to 5%/ft  obscura-
tion as described in the GEMINI 501 manual. Using the bowl shaped
applicator, apply aerosol until the panel alarms.

CLEANING

Before cleaning, notify the proper authorities that the system is undergo-
ing maintenance and will be temporarily out of service. Disable the sys-
tem to prevent unwanted alarms.

1. Remove the sensor to be cleaned from the system.

2. Remove the sensor cover, see Figure 4. Use a small standard screw-

driver to release each of the four cover removal tabs that hold the
cover in place.

3. Vacuum the outside of the screen carefully without removing it.

4. Remove the sensor screen. Pull the screen straight away from the

sensing chamber until it snaps out of place. Replacement screens
are available.

F300-15-00

       2

I56-036-00R

©2000 Fire•Lite

Figure 3. Test Magnet Positioning

Figure 4. Cleaning

5. Use a vacuum cleaner or clean, compressed air to remove dust and

debris from the sensing chamber.

6. Reinstall or replace the sensing chamber screen by sliding the edge

without the tabs over the sensing chamber. Make sure that one of the
screen contacts touches the circuit board contact.

7. Reinstall the sensor cover. Use the LEDs to align the cover with the

sensor. Snap the cover into place.

8. When all sensors have been cleaned, restore power to the system

and test the sensor(s) as described in the TESTING section of this
manual.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable  protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the following measures:

– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.

SENSOR
COVER

SENSOR
SCREEN

SENSING
CHAMBER

COVER REMOVAL
TABS

A78-2463-07

Please refer to insert for the Limitations of Fire Alarm Systems

;;;;;;

;;;;;;

yyyyyy

yyyyyy

;;;;;;;

;;;;;;;

yyyyyyy

yyyyyyy

LED 2

LED 1

PAINTED

SURFACE

TEST

MAGNET

PAINTED

SURFACE

TEST

MAGNET

Reviews: