2 Integrated Fire Protection System
Cycling Wet Pipe Systems
FM-072G-0-143 E
Page 1: ...intaining the fire protection system and devices in proper operating condition Refer to CONFIGURATION DESCRIPTION for maintenance instructions 4 General Description There are various types of wet pipe systems all of them using closed automatic sprinklers in the sprinkler piping This TOTALPAC2 integrated fire protection system by FireFlex Systems Inc consists of a cycling wet pipe system trim total...
Page 2: ...s been satisfied Should the fire rekindle the Firecycle III will initiate the sequence again This unique cycling feature will repeat as long as power is available to the panel helping to minimize water usage water damage and the danger of pollution to surrounding areas Firecycle III systems are also Fail Safe Note TOTALPAC2 Firecycle III Systems are available with electrical type release and the i...
Page 3: ...ivates latching normally open solenoid valve F1 closed Water discharges until all Firecycle Detectors have reset cooled below their set point After all detectors have reset the control panel activates the Soak Timer allowing the system to continue discharging water for a preset time period When the Soaking Timer has expired the control panel de energizes normally closed Release Solenoid Valve F2 a...
Page 4: ...larms it is important to remove trapped air from the system when filling it with water Air trapped in the system may also cause intermittent operation of the water motor gong during a sustained flow of water such as the flow required by an open sprinkler or the system test valve Consider installation of auxiliary vents to facilitate venting CAUTION Opening of the water supply main control valve A2...
Page 5: ...on Main Drain Test Riser Flow Test to determine if change in water supply or control valve position Test procedure Record the pressure indicated by the supply water gauge Fully open the main drain valve Record residual pressure Close the main drain valve slowly Record the time taken for supply water pressure to return to the original pressure Open the alarm control valve Semi Annually Valve superv...
Page 6: ...Page 6 of 6 TOTALPAC2 Integrated Fire Protection System Cycling Wet Pipe Systems FM 072G 0 143 E ...