F6.61 K-FACTOR TABLE (ONLY FOR FREQUENCY
OUTPUT)
K-Factor is the number of pulses which a sensor produces for one liter of
measured fluid. Here below all K-Factors for water at room temperature are
listed.
K-Factor values can depend on the installation conditions. K-Factor has to
divide the frequency generated by F6.61 in order to achieve the flow rate (l/s).
Please contact your dealer for K-Factor values not included in the table.
Metal Strap-on saddles
Part No.
DN/
Size
O.D.
min
O.D.
max K-Factor
SZIC080IHT
80
88
104
20,22
SZIC100IHT
100
112
126
12,99
SZIC125IHT
125
140
154
5,31
SZIC150IHT
150
168
234
3,67
SZIC200IHT
200
218
286
2,03
SZIC250IHT
250
272
344
1,31
SZIC300IHT
300
322
384
0,9
SZIC350IHT
350
425
458
0,67
SZIC400IHT
400
406
472
0,53
SZIC450IHT
450
475
516
0,4
Metal Strap-on saddles
Part No.
DN/
Size
d/R
K-Factor
SZIC080IHT
80
19,02
SZIC100IHT
100
11,28
SZIC125IHT
125
4,83
SZIC150IHT
150
3,31
SZIC200IHT
200
1,95
SZIC250IHT
250
1,24
SZIC300IHT
300
0,88
SZIC350IHT
350
0,73
SZIC400IHT
400
0,54
SZIC450IHT
450
-
Metal Strap-on saddles
Part No.
DN/
Size
d/R
K-Factor
WAIXHT
350
0,67
WAIXHT
400
0,53
WAIXHT
450
0,4
WAIXHT
500
0,34
WAIXHT
600
0,23
WAIXHT
700
-
WAIXHT
800
-
WAIXHT
900
-
Installation on cast iron pipes
Installation on other metal pipes
Installation on cast iron pipes