5.1 CONTROL PANEL
The control panel illustrated below is the only dryer-operator interface.
RD 185 - 810 - DMC14
K
2
set
DMC 14
°C
esc
°F
1
5
4
3
P
Q
S
0
0
0
9
RD 185 - 810 - DMC20
K
3
P
Q
S
0
0
1
0
1
Main switch
4
ON/OFF switch
2
Electronic control instrument (DMC14-DMC20)
with mains detecting light
3
Air and refrigerating gas flow diagram
5
Alarm light
5.2 OPERATION
Operating principal
-
The dryer models described in this manual operate all on the same principal. The hot moisture
laden air enters an air to air heat exchanger. The air then goes through the evaporator, also known as the air to
refrigerant heat exchanger. The temperature of the air is reduced to approximately 2°C, causing water vapor to condense
to liquid. The liquid is continuously coalesced and collected in the separator for removal by the condensate drain. The
cool moisture free air then passes back through the air to air heat exchanger to be reheated to within 8 degrees of the
incoming air temperature as it exits the dryer.
Refrigerant circuit
-
Refrigerant gas is cycled through the compressor and exits at high pressure to a condenser
where heat is removed causing the refrigerant to condense to a high-pressure liquid state. The liquid is forced through
a capillary tube where the resulting pressure drop allows the refrigerant to boil off at a predetermined temperature. Low-
pressure liquid refrigerant enters the heat exchanger where heat from the incoming air is transferred causing the
refrigerant to boil; the resulting phase change produces a low pressure, low temperature gas. The low-pressure gas is
returned to the compressor, where it is re-compressed and begins the cycle again. During those periods when the
compressed air load is reduced the excess refrigerant is by-passed automatically back to the compressor via the Hot
Gas By-pass Valve circuit.
Summary of Contents for RD 185-810
Page 39: ...40069 Zola Predosa BO ITALY info finicompressors it 7 1 7 RD 480 620 WC 7 1 8 RD 810 WC ...
Page 40: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 1 RD 185 410 ...
Page 41: ...40069 Zola Predosa BO ITALY info finicompressors it 7 2 2 RD 480 810 ...
Page 54: ...40069 Zola Predosa BO ITALY info finicompressors it The access code to the 2 level is 20 EN ...