User Manual EM735-Mod series
Document code: Fineco735-1-1.1 Revision2.001
Shanghai fangqiu electric CO.,LTD. Email:
Press “Page Down” button to decrease the digits. press ”Page Up” to increase the
digits press “SET” button to save the setup, the interface will switch to Baud rate setup
interface automatically. Press “SET” button to enter next interface if you do not need to
change the baud rate.
8.3 Baud rate setting
Press “Page down” and “page up” buttons to select the communication baud rate,
press “SET” button to save the setup. the interface will enter CT setup.
Remarks
default baud rate will be 1200bps.
8.4 CT rate setting
Press “Page down” and “page up” buttons to select the CT transformation ratio
press “SET” button to save the setup. the interface will enter Password setup.
CT
rate
5:5
5:50
5:60
5:75
5:10
0
5:125
5:150
5:
160
5
200
5:25
0
5:30
0
5:40
0
5:50
0
5:60
0
5:750
5:800
5:100
0
5
1200
5
1250
5
1500
5
2000
5
2400
5
2500
5:300
0
5:400
0
5:500
0
5
6000
5:75
00
Rem
ark
When CT ratio is lower than 200, there is 1digit decimals, when CT
ratio is equal or higher 200, there is no decimal.
Remark
1,if the meter is Direct connection type, it has no CT setup interface.
2,after the CT ratio setup, the energy consumption display will be reset to 0.
3.Default CT ratio is 5:5
l
Password setting
The meter will display the current password after enter the password setup
interface, press the “SET” to change the password. Use “page dow” and “page up”
button to input password as you want. After 30 seconds the meter will save the
password you changed.
Remarks:
1
Do not forget the password you setup.
2
Please press the button to check if every setup is correct after the program.
3
Password setup interface “-“ symbol will blink.