Fike Twinflex Multipoint 202-0003 Installation And Maintenance Instructions Download Page 4

 

 

26-0027 Issue 12

 

 

Remote Indicator 

 

The  remote  LED  terminals  (‘Remote  LED  +  /  -’)  may  be  used  to  connect  a  separate 
LED (Pt No. 600-0092). The LED functions are as follows: 

 

5ms every 5 seconds: End of Line 

 

5ms every 1.3 seconds: Fault 

 

350ms every 0.7 seconds: Fire detected by detector 

 

Continuous: Fire detected by detector and processed at panel 

Note that the LED does not require a resistor. 

 

 
Technical Data 

 

Dimensions 

 ................................................................. 105mm diameter x 62mm 

Operating temperature  

 ................................................................. -10

o

C to +50

o

Voltage Ranges 

DC Output from Mains Powered Panel ... 25.5 to 35V DC 

 

DC Output from Battery Powered Panel.. 20 to 26V DC 

Operating Current 

Quiescent ................................................ 114 uA (Typical) 

 

End of line ON if applicable ..................... 50 uA (Typical) 

 

(in addition to Quiescent) 

 

Alarm Sounding – Sounder High ............. 8 mA (Typical) 

 

Alarm Sounding – Sounder Low .............. 3.5 mA (Typical) 

 

Alarm Sounding – Sounder Off ............... 1.5 mA (Typical) 

 

Alarm Activated ....................................... 48.5 mA (Typical) 

 

(in addition to Alarm Sounding) 

LED Operation 

Detector in Normal State. ........................ Flash at 20 second intervals 

 

Detector at EOL ....................................... Flash at 5 second intervals 

 

 

Detector in Fault. ..................................... Flash at 1.3 second intervals 

 

 

Detector Detecting Fire ........................... Flash at 0.7 second intervals 

 

Detector in Fire 

(once processed at panel)

  Continuous 

Loading Units 

 

V3 Panel: 

Pro Panel: 

 

Max Loading Units per zone .................... 27 SLU ........ 160 DLU 

 

Sounder High ........................................... 1.5 SLU ....... 8.0 DLU  

 

Sounder Low ........................................... 1.0 SLU ....... 3.5 DLU  

 

No Sounder ............................................. 0.5 SLU ....... 1.5 DLU  

Volume Level 

Sounder High ........................................... 89+ dB(A)  

(@ 1m anechoic, Dual Tone)

 

Sounder Low ........................................... 65+ dB(A)  

Flammability 

. ................................................................ UL94-V2 

IP Rating 

. ................................................................ IP 21C 

Part Codes 

No Sounder ............................................. 202 0003 

 

With Sounder ........................................... 202 0001 

 
 

 

 

 

 

 

0832 

 

 

Fike Safety Technology Ltd, 

31 Springvale Ind Est, 

Cwmbran, UK. NP44 5BD 

 

(Manufactured Date on Product Label) 

 

0832-CPD-1572 
0832-CPD-1573 

 

 

EN54-3 Fire Alarm Device – Sounder 

Type A – Indoor Use 

EN54-5 Fire Alarm Device – Heat detector 

EN54-7 Fire Alarm Device – Smoke detector 

 

Sounder Technical Data: See 26-0747 

 

Technical Support 

 

Contact your supplier for technical support on this product. 

Due  to  the  complexity  and  inherent  importance  of  a  life  risk  type 
system,  training  on  this  equipment  is  essential,  and  commissioning 
should  only  be  carried  out  by  competent  persons.  Fike  cannot 
guarantee  the  operation  of  any  equipment  unless  all  documented 
instructions  are  complied  with,  without  variation.    This  unit  complies 
with the EMC directive. 
 
Fike’s policy is one of continual improvement and the right to change 
a specification at any time without notice is reserved. Whilst every 
care has been taken to ensure that the contents of this document are 
correct at time of publication, Fike shall be under no liability 
whatsoever in respect of such contents. E&OE.

 