26-1368-01
10
IVO Coil Output Connection (J5)
This Output circuit is used to energize the IVO coil to (electrically) activate the Impulse valve and dump
the Releasing agent. It is power limited and supervised. The EOL resistor (Fike part# 02-12225) and
blocking diode (Fike part# 02-1544) are mounted inside the IVO connector (Fike part# 17-0143) as
shown below. The assembly instructions are listed in Fike Connector Assembly Drawing No. 70-258.
The maximum cable length between the IVO and the IRM must not exceed 3 metres.
Figure 6
–
IVO Connections