background image

 

  Series Installation Guide 

Approved Document No: 26-1197 

AF&S

 

 

Issue: 1            Authorised:                  Date: 01/8/2013 

 
 
 

Drift Compensation Limit 

 

In the case of the smoke chamber reaching the end of it`s compensation limit, the detector will flash it`s LEDs continuously to signal that the 
detector should be replaced. This can be confirmed with the Sensitivity Test Wand. 
 

 

SPECIFICATION 

 

EN54-5/7 approval 
Supply Voltage:   

 

10.5~33V 

Alarm Current:   

 

20-24mA at 24 volts 

Quiescent Current:    

50uA Maximum 

Smoke Sensitivity:   

0.08 dB/m - 0.12 dB/m 

Temperature class:     

A2R (for OSCELUS-HR); A2S (for OCELUS-HF) 

Humidity Range: 

 

0% to 95% Relative Humidity, non condensing 

 

 

Maintenance Information 

 

OCELUS detectors are generally installed as part of a fire alarm system. 
Servicing of the system should be carried out in accordance with the requirements of the local code of practice for fire alarm installations, eg. BS 
5839 Part 1, Fire Detection and Alarm Systems for Buildings: Code of Practice for System Design, Installation and Servicing. 
The frequency of inspection testing will be based on a risk assessment of the installation, but should be no more than 6 months between visits. 
Over a 12 month period every detector should be functionally tested, using suitable equipment to generate smoke or heat (EG the Solo range from 
No Climb Products) 
All OCELUS smoke detectors have an IR transmitter that periodically transmits chamber data. This allows the detectors sensor status to be 
checked with a Sensitivity Test Wand. 

 

Cleaning 

 

Cleaning a smoke detector can prolong its working life. The detector can be cleaned with:- 
 

A hand held vacuum cleaner 

 

A clean air 

line or a “duster” aerosol 

 

A lint free cloth. 

The effectiveness of cleaning will depend on the operating environment of the detector. Depending on timescales & financial considerations, 
detector cleaning may not be a practical option. 
 

 

When to replace a detector 

 

A detector should be considered as needing to be replaced if:- 

 

The detector does not respond to a functional test 
If the Sensitivity Test Wand reports the chamber as bad 
If the detector has had an unexplained activation* 
If the detector has been in service for more than 10 years** 

 

* In some cases it may be sensible to leave a detector until a second unexplained activation, but consider the extra service costs and perceived 
system integrity if this is done. 

 

** Many detectors will continue to function adequately way beyond 10 years service. Balance the frequency of unwanted alarms, with the cost of 
replacing detectors when making this decision. 
 

 

 

 

 

 

 

 

EN54-5:2000+A1:2002   

Heat detectors — Point detectors 

 

EN54-7:2000+A1:2002 + A2: 2006 

Smoke detectors — Point detectors using scattered light, 

transmitted light or ionization 

 

OCELUS Conventional detectors 

200-0010, 200-0011, 200-0012 & 200-0013 

 

 

     

www.acornfiresecurity.com

www.acornfiresecurity.com

Reviews: