SPACING

Wireless technologies can exhibit communication disruption if devices are 
spaced too close together. To avoid this form of disruption, SWIFT devices 
should not be placed closer than 2 feet (60 cm) apart without an intervening 
structure.

MOUNTING

The FIK-W-MONITOR mounts directly to an SMB500-WH electrical box. (See 
Figure 4.) To avoid interference with the wireless network metal electrical 
boxes are NOT recommended. Non-metal surface mounted electrical boxes 
(SMB500-WH) are available from Fike. If not using an SMB500-WH, the mini-
mum mounting opening dimensions for the FIK-W-MONITOR are 4 in. X 3¾ 
in. x 1½ in. deep. 

NOTE: Do not attach the module to temporary structures such that the place-
ment could be altered.

WIRING

NOTE: All wiring must conform to 
applicable local codes, ordinances, 
and regulations. This module is in-
tended for power limited wiring only. 
FIK-W-MONITOR must be within 3 
feet of monitored device when using 
field wiring or 20 feet in non-metallic 
conduit.

1.   Install module wiring in accor-

dance with the job drawings 
and appropriate wiring dia-
grams.

2.   Set the address on the module 

per job drawings.

3.   

Secure module to electrical 
box (supplied by installer), as 
shown in Figure 4.

C1096-00

C1097-00

FIGURE 4. MODULE MOUNTING

FIGURE 3. BATTERY COMPARTMENT

BATTERY
COMPARTMENT
DOOR

BATTERY
COMPARTMENT

C2002-00

FIGURE 5. TYPICAL MONITORING CONFIGURATION

WIRELESS 

MONITOR MODULE

ONLY ONE UL LISTED CONTACT 

CLOSURE MAY BE USED

POWER LIMITED

3.1 VDC MAX

3.9K EOL 

RESISTOR 

A2143-10

INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S 

INSTALLATION INSTRUCTIONS. WIRELESS MONITOR MODULE MUST BE 

WITHIN 3 FEET OF MONITORED DEVICE WHEN USING FIELD WIRING 

OR 20 FEET IN NON-METALLIC CONDUIT.

C1099G-00

FCC STATEMENT

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void 
the user’s authority to operate the equipment.

LICENSING STATEMENT

Use of these products in combination with non-Honeywell products in a wireless mesh network, or to access, monitor or control devices 
in a wireless mesh nework via the internet or another external wide area network, may require a separate license from Sipco, LLC. 
For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900, Suite 950, Atlanta, GA 303350, or at www.
sipocollc.com or www.intusiq.com.

SUPPLEMENTAL INFORMATION

For Limitations of Fire Alarm Systems, 

please go to: 

http://www.systemsensor.com/

en-us/Documents/I56-1558.pdf  

 

Limitations of  

Fire Alarm Systems

  2 

I56-6962-000 

  

©2021. 1/19/2021

Fike

®

 is a registered trademark of Fike Corporation. SWIFT

®

 and System Sensor® are registered trademarks of Honeywell International, Inc. 

Reviews: