SPACING
Wireless technologies can exhibit communication disruption if devices are
spaced too close together. To avoid this form of disruption, SWIFT devices
should not be placed closer than 2 feet (60 cm) apart without an intervening
structure.
MOUNTING
The FIK-W-MONITOR mounts directly to an SMB500-WH electrical box. (See
Figure 4.) To avoid interference with the wireless network metal electrical
boxes are NOT recommended. Non-metal surface mounted electrical boxes
(SMB500-WH) are available from Fike. If not using an SMB500-WH, the mini-
mum mounting opening dimensions for the FIK-W-MONITOR are 4 in. X 3¾
in. x 1½ in. deep.
NOTE: Do not attach the module to temporary structures such that the place-
ment could be altered.
WIRING
NOTE: All wiring must conform to
applicable local codes, ordinances,
and regulations. This module is in-
tended for power limited wiring only.
FIK-W-MONITOR must be within 3
feet of monitored device when using
field wiring or 20 feet in non-metallic
conduit.
1. Install module wiring in accor-
dance with the job drawings
and appropriate wiring dia-
grams.
2. Set the address on the module
per job drawings.
3.
Secure module to electrical
box (supplied by installer), as
shown in Figure 4.
C1096-00
C1097-00
FIGURE 4. MODULE MOUNTING
FIGURE 3. BATTERY COMPARTMENT
BATTERY
COMPARTMENT
DOOR
BATTERY
COMPARTMENT
C2002-00
FIGURE 5. TYPICAL MONITORING CONFIGURATION
WIRELESS
MONITOR MODULE
ONLY ONE UL LISTED CONTACT
CLOSURE MAY BE USED
POWER LIMITED
3.1 VDC MAX
3.9K EOL
RESISTOR
A2143-10
INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S
INSTALLATION INSTRUCTIONS. WIRELESS MONITOR MODULE MUST BE
WITHIN 3 FEET OF MONITORED DEVICE WHEN USING FIELD WIRING
OR 20 FEET IN NON-METALLIC CONDUIT.
C1099G-00
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void
the user’s authority to operate the equipment.
LICENSING STATEMENT
Use of these products in combination with non-Honeywell products in a wireless mesh network, or to access, monitor or control devices
in a wireless mesh nework via the internet or another external wide area network, may require a separate license from Sipco, LLC.
For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900, Suite 950, Atlanta, GA 303350, or at www.
sipocollc.com or www.intusiq.com.
SUPPLEMENTAL INFORMATION
For Limitations of Fire Alarm Systems,
please go to:
http://www.systemsensor.com/
en-us/Documents/I56-1558.pdf
Limitations of
Fire Alarm Systems
2
I56-6962-000
©2021. 1/19/2021
Fike
®
is a registered trademark of Fike Corporation. SWIFT
®
and System Sensor® are registered trademarks of Honeywell International, Inc.