FIK-UV-IR-HD
User Manual
Doc. No. 06-935.02
For more information & Technical support: (800)-979-FIKE (3453)
1
1.
Introduction
The FIK-UV-IR-HD flame detector provides ultra-fast response, high performance and reliable detection of a
large variety of fires including hydrocarbon fires (visible and non-visible), as well as hydrogen fires.
The detector addresses slow growing fires as well as fast eruptions of fire using improved UV-IR technology.
The detector operates in all weather and light conditions. The detector provides high-definition (HD) video
output of the monitored area with clear imaging of a fire event and of personnel at distances up to 100 ft
(30m) allowing rescuers to discover the exact situation before entering the hazardous area. It will
automatically record a video of a fire event (1 min pre-alarm/up to 3 mins post-alarm).
The integral HD quality video, with event recording, on top of the proven superior capabilities of UV-IR flame
detection together provide a very powerful safety tool to protect your personnel, plant and process.
This manual covers two UV/IR detector models:
1.
FIK-UV-IR-HD
: Hydrogen and hydrocarbons flame detection. Spectrum response of IR radiation in the
3.0-4.0-micron range.
2.
FIK-UV-IR-F-HD
: Hydrocarbon flame detection. Spectrum response of IR radiation in the 4.0-5.0-
micron range
1.1
Key Features
•
High immunity
: To false alarm
•
Ultra-fast detection mode
: Within 5 milliseconds for Hydrogen fireballs or explosions
•
Hydrogen and hydrocarbons flame detection
•
High sensitivity
: Up to 100 ft. (30m) for a 1ft2 (0.1m2) n-heptane pan fire
•
HD video output
: With automatic HD video recording of fire events
•
Data/Event logger
: Alarms, faults and other relevant events are logged to non-volatile memory
•
Ethernet communication
: In addition to the standard methods, such as 4-20mA and Modbus
•
Built-in-Test (BIT)
: Automatic and manual internal self-test of window cleanliness and the overall
operation of the detector (for both IR and UV channels)
•
Window heater
: To avoid condensation and icing
•
Tilt mounting bracket
: Can be connected either above or below the detector
•
UV and IR warning levels - 0-20mA
- current output warning when elevated UV or IR radiation is
detected.