background image

I56-6638-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

R

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

 

FIK-PC351  

Multi-Criteria Photoelectric  

and CO Sensor 

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:   200 uA (one communication every 5 sec. with green LED blink on communication)

Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

15% to 90% Relative Humidity, Non-condensing

Operating Temperature Range:  32°F to 122°F (0°C to 50°C)

Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Height: 

2.7˝ (69 mm) installed in B200S series sounder base

Diameter: 

6.875˝ (175 mm) installed in B200S series sounder bases

Weight: 

3.4 oz. (95 g) 

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions.

CO detector spacing, placement and special applications, refer to NFPA 72, 
NFPA 720, and the System-Connected Carbon Monoxide Detectors Application 
Guide also available from System Sensor.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. 
Improper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the base wiring diagram. 

(See Figure 1.) 

2.   Set the desired address on the sensor address switches. (See Figure 2.)
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

FIGURE 1. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL LISTED COM

PA

TIBLE

CONTR

OL 

PA

NE

L

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)
(+)

C0129-04

CAUTION

Do not loop wire under terminal 1 or 2. Break wire run to provide supervision 
of connections.

FIGURE 2. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

UL 2075 listed for Carbon Monoxide
UL 268 listed for Open Air Protection
This sensor must be installed in compliance with the control panel system 
installation manual. For local audible indication of a fire and/or carbon 
monoxide alarm, it is recommended to install the multi-criteria photoelec-
tric and carbon monoxide (CO) sensor into a B200S series sounder base. 
If a local audible device is not used, care should be taken to develop a 
proper response plan. The installation must meet the requirements of 
the Authority Having Jurisdiction (AHJ). Sensors offer maximum per-
formance when installed in compliance with the National Fire Protec-
tion Association (NFPA); see NFPA 72 and NFPA 720. For a complete list 
of compatible bases, refer to the Base/Sensor Cross Reference Chart at 

 

systemsensor.com.

GENERAL DESCRIPTION

Model FIK-PC351 is a plug-in type multi-criteria smoke sensor that offers a 
photoelectric sensing chamber combined with a carbon monoxide (CO) sen-
sor as well as a carbon monoxide detector. 
All sensors transmit an analog representation of smoke and/or carbon monox-
ide density over a communication line to a control panel. Rotary dial switches 
are provided for setting the sensor’s address. (See Figure 2.) 
Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 
Fike panels offer different features sets across different models. As a result, 
certain features of the photoelectric and CO sensors may be available on some 
control panels, but not on others. 
The multi-criteria photoelectric and CO sensor only supports Fike IDP mode 
systems. The possible features available to FIK-PC351, if supported by the 
control unit are:
1.   The sensor’s LEDs can operate in three ways—on, off, and blinking—and 

they can be set to red, green, or amber. This is controlled by the panel. 

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for specific 
operation. The multi-criteria photoelectric and CO sensor requires compatible 
addressable communications to function properly. Connect these sensors to 
listed-compatible control panels only. 

SPACING

Fike recommends spacing smoke detectors in compliance with NFPA 72. In 
low air flow applications with smooth ceilings, space sensors 30 feet apart 
(9.1 m). For specific information regarding sensor spacing, placement, and 
special applications, refer to NFPA 72 and the System Smoke Detector Applica-
tion Guide, available from System Sensor. For specific information regarding 

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6638-000 

 

 1/15/2021

Summary of Contents for FIK-PC351

Page 1: ...iance with the control panel system installation manual For local audible indication of a fire and or carbon monoxide alarm it is recommended to install the multi criteria photoelec tric and carbon monoxide CO sensor into a B200S series sounder base If a local audible device is not used care should be taken to develop a proper response plan The installation must meet the requirements of the Author...

Page 2: ...t The magnet test initiates an approximately 10 minute period when the detec tor s signal processing software routines are not active Once in test mode test the smoke detector using one of the tested and ap proved aerosol smoke products Refer to the manufacturer s published instruc tions for proper use of the canned smoke agent When used properly the canned smoke agent will cause the smoke detecto...

Page 3: ...s Carbon monoxide gas is a highly poisonous gas which is released when fuels are burnt It is invisible has no smell and is therefore impossible to detect with the human senses Under normal conditions in a room where fuel burn ing appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be danger ous SYMPTOMS OF CARBON MON...

Page 4: ...e and 2 this device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates use...

Reviews: