Fike FIK-IR3-HD User Manual Download Page 21

 

FIK-IR3-HD 

User Manual

  

Doc. No. 06-932.02 

 

 

For more information & Technical support: (800)-979-FIKE (3453)

 

15

 

 

 

 

5

 

Operation  

The FIK-IR3-HD is a triple-IR flame detector that includes a built-in high-definition video camera module. The 

video module automatically records video of alarm events, and can provide live video of the detection zone 
to a screen in the control room.  

The detector is ready for detecting fire approximately 30 seconds after power up. During this startup time the 

LED flashes Yellow. If the startup is successful, the indication LED turns to green, the 0-20mA indicates 4mA 
and the fault relay is closed. The video module starts operating approximately 2 minutes after power up.  

Detector configuration settings can be changed as described in section 3.

 

 

To restart the detector, turn off and then turn on the power.   

 

5.1

 

Output Signals  

The detector has the following output signals:  

 

Current output (0–20mA)  

 

Relays (Fault and Alarm)  

 

RS-485  

 

Tri-color LED  
  

Table 4 - Output Signals 

  

Startup  

Fault  

Dirty 

Window  

Normal  

Fire Alarm  

0 – 20mA 

 

1mA 

 

1mA 

 

2mA 

 

4mA 

 

20mA 

 

Fault Relay (NO) 

 

Open 

 

Open 

 

Open 

 

Closed 

 

Closed 

 

Alarm Relay NO 

 

Open 

 

Open 

 

Open 

 

Open 

 

Closed 

 

LED 

 

Flashing 

Yellow  

 

Flashing 

Yellow 

 

Yellow 

 

Green 

 

Red 

 

  

5.2

 

Testing  

The detector has a Built-In-Test (BIT) capability to ensure proper operation and to make sure that the window 

is not dirty. The BIT process runs automatically at startup and periodically during the operation of the 
detector. The BIT can also be initiated manually by short circuiting the “Manual BIT” terminal and the “24 
VDC (-)“ terminal for one second (see Table 3) or by using the communicator software (connected through 
RS-485).  

In case of “Dirty Window” fault the detector may still detect flames but at a lower sensitivity.  

 

 

Summary of Contents for FIK-IR3-HD

Page 1: ...FIK IR3 HD User Manual Doc No 06 932 02 704 SW 10th St Blue Springs MO 64014 USA T 1 816 229 3405 www Fike com FIK IR3 HD Triple IR Flame Detector...

Page 2: ......

Page 3: ...to use the specified equipment No part of this publication may be reproduced or transmitted for commercial purposes such as selling copies of this publication or for providing paid for support service...

Page 4: ...4 Certification Instructions 4 2 5 Installing the Tilt Mount 4 2 6 Installing the detector 6 3 Configuration options 7 3 1 Sensitivity 7 3 2 Ultra Fast Detection 8 3 3 Alarm Delay 8 3 4 Alarm Latch 8...

Page 5: ...6 2 Video functionality 18 6 3 Electrical Specifications 18 6 4 Outputs 18 6 5 Mechanical Specifications 19 6 6 Environmental Specifications 19 6 7 Label Figures 20 6 8 Approvals 21 6 9 Electromagneti...

Page 6: ...ew 5 Figure 3 Detector on Tilt Mount Side View 6 Figure 4 Source 4 Wire Scheme 12 Figure 5 Sink 4 Wire Scheme 12 Figure 6 Source 3 Wire Scheme 13 Figure 7 Sink 3 Wire Scheme 13 Figure 8 RS 485 Network...

Page 7: ...er provide additional means to study the cause and development of fire events 1 1 Key Features Extreme sensitivity up to 260ft 80m for a 1 ft2 0 1m2 N heptane pan fire 1 5 second detection time for 1...

Page 8: ...ossible the detector face should be tilted aimed down at an angle to prevent the accumulation of dust and dirt Do not start an installation until the detector task definition system configuration inst...

Page 9: ...f general purpose common tools and equipment Prior to installation Verify the appropriate purchase order Record the part and serial numbers of the detectors and the installation date and log Visually...

Page 10: ...r example regular checks as part of routine inspections or establishing from the material s data sheet that it is resistant to specific chemicals 2 4 1 Specific conditions for use The equipment is not...

Page 11: ...gnated location and secure it with four screws through four 0 28 7mm diameter holes There are four captive screws with spring washers in the tilt mount The following drawing shows the location of the...

Page 12: ...les you to rotate the detector e Point the detector towards the detection area and make certain that the view of the area is unobstructed f Secure the detector in that position by tightening the locki...

Page 13: ...ay Alarm latch Disabled Enabled Disabled Window heater Disabled Enabled Enabled Video module Disabled Enabled Enabled Post alarm video recording duration 1 2 or 3 minutes 1 minute Video analog output...

Page 14: ...still detected the alarm outputs are activated 3 4 Alarm Latch If alarm latch is enabled the detector outputs will remain in alarm mode even after a flame is no longer detected To return the detector...

Page 15: ...h a unique Modbus address The address of the detector can be set to any value in the range 1 247 3 8 Manual BIT Alarm Output Test When enabled the alarm outputs are activated when a Manual BIT is init...

Page 16: ...support 800 979 FIKE 3453 10 4 Detector Wiring WARNING The sensor module in the front half of the detector contains no serviceable components and should never be opened The terminal compartment at the...

Page 17: ...normally open SPST contact relay that is open in normal operation and closed when fire is detected This relay can be configured to latch as described in section 3 4 8 Alarm Relay COM 9 Analog Video C...

Page 18: ...r 4 wire connected The following drawing shows how to wire the detector to act as a current source isolated transmitter 4 wire connection Figure 4 Source 4 Wire Scheme The following drawing shows how...

Page 19: ...ability of the detector and communicator software it is possible to connect up to 32 detectors in an addressable system with 4 wires only 2 for power and 2 for communication Using repeaters the number...

Page 20: ...FIK IR3 HD User Manual Doc No 06 932 02 For more information Technical support 800 979 FIKE 3453 14 Figure 8 RS 485 Networking...

Page 21: ...3 To restart the detector turn off and then turn on the power 5 1 Output Signals The detector has the following output signals Current output 0 20mA Relays Fault and Alarm RS 485 Tri color LED Table 4...

Page 22: ...tenance After powering up the detector should work maintenance free with the exception of optical window cleaning and an annual fire detection operational test WARNING The sensor module in the front h...

Page 23: ...6 3 Yellow LED constantly on Fault Relay is open 0 20mA at 2mA BIT Fault Clean detector window Restart the detector by turning the power off and then back on Red LED constantly on Detector is in alar...

Page 24: ...en Network Video Interface Forum Profile S 6 3 Electrical Specifications Operating Voltage 24 VDC nominal 18 32 VDC Current Consumption Standby 180mA Maximum 250mA all systems in operation including w...

Page 25: ...on RS 485 Digital Video IP network IEEE 802 3 10 Base t 6 5 Mechanical Specifications Size 7 87 x 5 12 5 12 200 130 130mm Weight Detector Stainless Steel 316 9 8 lbs 4 4 kg Tilt mount Stainless steel...

Page 26: ...FIK IR3 HD User Manual Doc No 06 932 02 For more information Technical support 800 979 FIKE 3453 20 6 7 Label Figures 6 7 1 Ex db...

Page 27: ...C Ex db IIB T4 Gb 50 C Ta 85 C FM FMC Class I Div 1 Groups B C D T4 Class I Zone 1 AEx Ex db IIB T4 Gb T4 50 C Ta 85 C T5 50 C Ta 75 C Performance ANSI FM 3260 EN 54 10 6 9 Electromagnetic Compatibili...

Page 28: ...r or replace it at its sole discretion if found to have been defective when shipped Said repair or replacement is FIRE GAS DETECTION TECHNOLOGIES INC s sole liability under this warranty and transferr...

Page 29: ...ity Fuel Size Distance ft m Average Response Time Seconds N Heptane 1 x 1 ft 262 80 9 0 N Heptane 1 x 1 ft 230 70 4 1 N Heptane 1 x 1 ft 98 30 1 5 Gasoline 1 x 1 ft 230 70 3 6 Gasoline 2 x 2 ft 328 10...

Page 30: ...32 plume 82 25 0 8 LPG 32 plume 98 30 1 4 Diesel 1 x 1 ft 79 24 3 9 JP5 1 x 1 ft 79 24 1 9 Kerosene 1 x 1 ft 79 24 2 5 Methanol 1 x 1 ft 75 23 1 2 Ethanol 1 x 1 ft 75 23 1 6 Isopropanol 1 x 1 ft 75 2...