Section 3: Hardware Installation
The FIK-5496 installation involves the following steps:
1.
Connect the AC power (Section “AC Power” on page 11) and the backup battery (Section “Battery Connection” on page 11).
2.
Make the physical connection to a Fike addressable FACP (see Section “Connecting the FIK-5496 to the FACP” on page 12).
3.
Set an ID for the FIK-5496 (Section “Setting the Device ID” on page 12).
4.
Make the physical connection to any outputs that will be powered by this FIK-5496. See Section “Notification Appliance Wiring” on
page 13 for the notification appliance wiring information. For information on the software configuration and other installation output
information, refer to Section 1.3 for a list of the Fike Addressable FACP Installation Manuals that can be found on Fike’s website at
www.fike.com.
3.1 AC Power
At the installation, connect the AC terminals to 120 VAC source as shown in “AC Power Connection” on page 11. It may be necessary for a
professional electrician to make this connection. The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.5 A.
.
Figure 3.1 AC Power Connection
3.2 Battery Connection
The following list the battery connection requirements.
•
The FIK-5496 battery charge capacity is 7.0 AH not to exceed 35.0 AH.
•
Use 12V batteries of the same AH rating.
It is recommended that you replace the batteries every five years.
•
Determine the correct AH rating per your current load calculation (see “: Current Draw Calculation Worksheet” on page 6).
Wire the batteries in series to produce a 24-volt equivalent. Do not parallel the batteries to increase the AH rating.
.
Figure 3.2 Battery Connection
To AC
To 120 VAC
Power Source
Supervised
Non-power-limited
NOTE:
If you require the power of the back-up batteries that are too large for the FIK-5496, you can use the FIK-RBB cabinet. The FIK-RBB
Remote Battery Box, holds batteries up to the 35 AH size. (Refer to P/N 151306 for FIK-RBB Installation Instructions.
Red
To Panel
Black
UL Listed 12V Battery
UL Listed 12V Battery
Battery
Jumper
(P/N 140694)
Shipped with
the FIK-5496
Supervised
Non-Power-Limited
Replace batteries every 5 years.
Gell Cell
Gell Cell