FIGURE 1: WALL MOUNTING PLATE
FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS
CONNECTING THE AIR SAMPLING PIPE
ATTENTION
Detailed pipe network information and best practices can be found in the
Pipe Installation Guide, available for download at systemsensor.com/faast
The input and output ports are designed to accept nominal one inch pipe
(25mm). The input and output ports are tapered to provide fast, easy, pushfit
connection of the sampling pipe to the unit. Perform the following procedure
to connect the air sampling pipe to the unit.
1. Square off and de-burr the end of the sampling pipe. Ensure that the
pipe is free from any particles that might interfere with the pipe con-
nection.
2. Remove the input plug from the input port being used (either the top
or bottom of the unit).
3. Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
EXHAUST PIPE
The device should always be exhausted in to the space that it is monitoring.
There are some circumstances where it may be necessary to connect a pipe to
the exhaust port to divert the exhaust away from the location of the unit. Add-
ing as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring
quieter operation. The output ports are tapered the same as the input ports, to
provide fast, easy, push-fit connection of an exhaust pipe to the unit. Perform
the following procedure to connect the exhaust pipe to the unit.
1. Square off and de-burr the end of the sampling pipe. Ensure that the
pipe is free from any particles that might interfere with the pipe con-
nection.
2. Remove the input plug from the input port being used (either the top
or bottom of the unit).
3. Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
WIRING
WARNING
Before working on the FAAST XT system, notify all required authorities that
the system will be temporarily out of service. Make sure all power is removed
from the system before opening the unit. All wiring must be in accordance
with local codes.
POWER CABLES
Use the power ratings of the unit to determine the required wire sizes for each
connection. Use the power ratings of the connected products to determine the
wire size.
CONDUIT USAGE
If electrical conduit is used for system wiring, terminate the conduits at the
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.
1. Run all wiring, both power and alarm, through the conduit and into
the left side of the unit enclosure, as seen in Figure 3.
2. Attach the appropriate wires to the supplied Euro connector. Follow
appropriate local codes and electrical standards for all cabling.
3. Plug the appropriate connector into the mating connector on the unit.
ASP115-00
ASP116-00
FK-600-000 2 I56-4223-001
MOUNTING THE DETECTOR TO THE BRACKET
Once the mounting plate is attached, the unit is ready to be mounted on to the
plate. Perform the following procedure to mount the unit.
1. Before installing the unit onto the bracket, remove the appropriate
conduit caps from the top or bottom left side of the unit to match the
orientation of the wiring. See Figure 4 for location of the wiring access
plugs.
2. Line up the unit with the four mounting clips and the mounting studs
on the left side.
3. Push the unit down onto the mounting clips and secure it with the
supplied washer and nut on the mounting stud protruding through the
mounting slot shown in Figure 2.