background image

FIGURE 1: WALL MOUNTING PLATE

FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS

CONNECTING THE AIR SAMPLING PIPE

ATTENTION

Detailed pipe network information and best practices can be found in the
Pipe Installation Guide, available for download at systemsensor.com/faast

The input and output ports are designed to accept nominal one inch pipe 
(25mm). The input and output ports are tapered to provide fast, easy, pushfit 
connection of the sampling pipe to the unit. Perform the following procedure 
to connect the air sampling pipe to the unit.
 

1.  Square off and de-burr the end of the sampling pipe. Ensure that the 

pipe is free from any particles that might interfere with the pipe con-
nection.

 

2.  Remove the input plug from the input port being used (either the top 

or bottom of the unit).

 

3.  Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT 

glue these pipes.

EXHAUST PIPE

The device should always be exhausted in to the space that it is monitoring. 
There are some circumstances where it may be necessary to connect a pipe to 
the exhaust port to divert the exhaust away from the location of the unit. Add-
ing as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring 
quieter operation. The output ports are tapered the same as the input ports, to 
provide fast, easy, push-fit connection of an exhaust pipe to the unit. Perform 
the following procedure to connect the exhaust pipe to the unit.
 

1.  Square off and de-burr the end of the sampling pipe. Ensure that the 

pipe is free from any particles that might interfere with the pipe con-
nection.

 

2.  Remove the input plug from the input port being used (either the top 

or bottom of the unit).

 

3.  Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT 

glue these pipes.

WIRING

WARNING

Before working on the FAAST XT system, notify all required authorities that 
the system will be temporarily out of service. Make sure all power is removed 
from the system before opening the unit. All wiring must be in accordance 
with local codes.

POWER CABLES

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine the 
wire size.

CONDUIT USAGE

If electrical conduit is used for system wiring, terminate the conduits at the 
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.

 

1.  Run all wiring, both power and alarm, through the conduit and into 

the left side of the unit enclosure, as seen in Figure 3.

 

2.  Attach the appropriate wires to the supplied Euro connector. Follow 

appropriate local codes and electrical standards for all cabling.

 

3. Plug the appropriate connector into the mating connector on the unit.

ASP115-00

ASP116-00

FK-600-000  2 I56-4223-001

MOUNTING THE DETECTOR TO THE BRACKET

Once the mounting plate is attached, the unit is ready to be mounted on to the 
plate. Perform the following procedure to mount the unit.

 

1.  Before installing the unit onto the bracket, remove the appropriate 

conduit caps from the top or bottom left side of the unit to match the 
orientation of the wiring. See Figure 4 for location of the wiring access 
plugs.

 

2.  Line up the unit with the four mounting clips and the mounting studs 

on the left side.

 

3.  Push the unit down onto the mounting clips and secure it with the 

supplied washer and nut on the mounting stud protruding through the 
mounting slot shown in Figure 2.

Reviews: