ECS Series Manual —
P/N LS10262-001FK-E:A 3/3/2021
49
Installing the FIK-DUAL50W
Device Installation
3.
Secure the supplied bracket to the top mounting bracket on the FIK-DUAL50W with the two mounting screws. See Figure 4.43.
Figure 4.43 FIK-DUAL50WBD Mounting Bracket
4.
Align the mounting holes on the bracket with the enclosure.
5.
Secure the board to the enclosure.
6.
Restore AC power and reconnect the backup batteries.
Figure 4.44 FIK-DUAL50WBD In Enclosure
4.7.4 Wiring Specifications
All wiring and devices installed in the system must meet the standards described in National Electrical Code (NFPA 70), NFPA Standard 72,
and Life Safety Code (NFPA 101).
To avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated from high-current output and
power wiring. Avoid pulling one multi-conductor cable for the entire panel.
Instead, separate the wiring as follows:
Mounting
bracket
1/4” spacing must be maintained
Input/Output Type:
Wiring
between each of these circuit types;
Non Power-Limited:
AC power, Standby batteries
as well as between power limited
Power-Limited:
SBUS, VBUS
and non power-limited circuits.
Audio:
Speaker