background image

BECAUSE SO MUCH IS AT STAKE™

 

Application Guide 

 
 

Form No.  06-795, Rev. 0 (02/16) 

 

Page 1 of 8 

 

Figure 1 - Model TA-123PP 

Cheetah

®

 Xi and SHP-Pro

®

 Purge Operation 

The National Fire Protection Association (NFPA) standards associated with gaseous fire suppression systems (e.g., 
carbon dioxide and clean agent) stipulate that suitable steps and safeguards shall be taken to prevent injury or death 
to personnel in areas whose atmospheres will be made hazardous by the discharge or thermal decomposition of the 
agent. One of the recommended safeguards includes providing a means for prompt ventilation (purge) of the fire zone 
after an event has occurred. 

In the past, Fike offered a self-contained purge panel (P/N 10-045) that could be installed to meet this requirement; 
however, the purge panel has been discontinued and is no longer available from Fike. This does not mean that Fike’s 
releasing systems are no longer able to comply with the purge requirement. It simply means that an alternate method 
must be used, as described in this application guide, to accomplish the purge requirement. There are two options that 
can be used to perform the purge function with Fike’s suppression panels.  

Option 1 

The first option is to purchase and install the Purge Panel Controller, model TA-
123PP, manufactured by Light Engineered Displays, Inc. (See Figure 1). One 
controller must be purchased for each suppression zone and external field 
relays must be installed to control the purge components.  The L.E.D. purge 
controller has been tested by Fike for compatibility and correct operation with 
both the Cheetah Xi (including 50 point) and SHP-Pro panels. The purge 
controller must be purchased directly from L.E.D. and not from Fike.  

Note:

 

This is the only option for performing purge with the SHP-Pro panel.

 

Option 2 

The second option is to utilize the following Cheetah Xi components to accomplish the purge functionality. 

2 ea. 55-043 relay module,  

1 ea. 55-045 mini-monitor module,  

1 ea. 20 Zone annunciator 10-2667,  

1 ea. Key-Switch (non-latching capable)* 

*

The 10-1642 Keyed Abort or 10-2705 Solenoid Disconnect switches can be used for this purpose but would need to 

re-label for purge functionality. 

General Purge Sequence of Operation 

Upon the suppression zone entering into the “Release State”, the following shall occur: 

1.  A relay module configured for “Release” for the active suppression zone will activate. The relay shall be 

configured with a time delay (0 to 80 minutes) for “Purge Soak”.  

2.  An LED on a twenty-zone annunciator will illuminate to indicate the start of the “Purge Soak” period for the 

suppression zone.  

3.  Upon completion of the “Purge Soak” timer, the relay module’s contacts (item 1) will transfer sending a 

“Process” input to the panel via the modules feedback input. This input will be the first interlock required to 
initiate purge operation. 

4.  An LED on a twenty-zone annunciator will illuminate to indicate the completion of the “Purge Soak” period and 

the ready state of the purge system. 

5.  Upon activation of a purge key-switch (non-latching) configured for the suppression zone, a “Process” input 

will be sent to the panel. This input will be the second interlock required to initiate purge operation. 

Summary of Contents for Cheetah Xi

Page 1: ...roller has been tested by Fike for compatibility and correct operation with both the Cheetah Xi including 50 point and SHP Pro panels The purge controller must be purchased directly from L E D and not from Fike Note This is the only option for performing purge with the SHP Pro panel Option 2 The second option is to utilize the following Cheetah Xi components to accomplish the purge functionality 2...

Page 2: ...mple shows how to program the Cheetah Xi components to accomplish purge operation For this example the purge operation shall be configured for Zone 1 The first addressable relay module shall be utilized to initiate the Purge Soak period for Zone 1 For this example the module shall be assigned to Loop 1 Address 8 The relay module shall be programmed as follows See Figures 2 and 3 1 With the Common ...

Page 3: ...nfiguration options should be left at default settings Figure 3 Relay Module Configured for Purge Soak Period One of the normally open relay contacts on the relay module must be wired to the feedback input on the module as shown in Figure 4 below Upon expiration of the relay s internal timer the modules relay contacts will transfer causing activation of the modules feedback input This will cause a...

Page 4: ... start the purge function Activation of the purge key switch prior to expiration of the Purge Soak timer will only initiate a process input to the panel The second addressable relay module shall be utilized to activate the mechanical components associated with Zone 1 purge operation i e fans dampers etc Activation of this relay shall be triggered by the expiration of the Purge Soak relay timer and...

Page 5: ... Row B to 4 Row two of the Output Control table should indicate Group P3 P4 9 Select priority Row 3 and set the Activation State option to Process Action Type option to Activate on Specific Device and Relay State option to OFF 10 Upon setting the relay action type to Activate on Specific Device loop and address selection fields will appear at the bottom of the configuration screen Set these fields...

Page 6: ... same programming process Purge System Status Indication In order to provide visual indication of the status of the purge system operation Fike s 20 Zone remote LED annunciator can be used See Figure 8 For this example the annunciator shall be programmed as follows See Figures 9 and 10 1 Configure LED 01 for ON Zone Release for Zone 1 The yellow LED will turn on upon Zone 1 entering the release st...

Page 7: ...clarification Design Note Where the system incorporates more than one suppression zone additional relay modules monitor modules and key switches must be added for each additional suppression zone The programming should follow the same general convention shown in this application guide Please feel free to contact Fike s electrical support at 1 800 979 3453 option 2 1 if you have any questions regar...

Page 8: ...MPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A SPECFIC PURPOSE You should not act on any information products or services described herein before you have formed your own opinion through investigation and research as to the suitability of the information products or services for your specific application and circumstances Fike 704 SW 10 th Street P O Box 610 Blue Springs Missouri 64013 0610...

Reviews: