26-1029 Issue 6 

The  Loop +ve (positive) IN and the Loop +ve (positive) OUT  connections are split within the module. For cable 
continuity readings at the commissioning stage they must be temporarily removed and connected through. Please 
remember that all high voltage testing must be carried out before the installation of the electronics, otherwise the 
electronics will be damaged. Please also note that the SCRN terminal should only be connected to the loop screen 
and NOT the building earth. 
 
Once all testing has been carried out on the cabling and 

continuity & insulation

  has been proven,  the 

Sounder/Strobe unit can be assembled. 
 
NOTE: Before installing the Sounder/Strobe remember to note the serial number of the device (located on the rear 
of the unit) on to your drawings or configuration sheets to enable you to prove its location later. The address 
allocation for the device is carried out automatically by the control panel whilst in initialisation mode, so addresses 
do not need to be set manually. See the system Installation and Operating Instructions for further details. 
 

Tamper Resistance 

 
The unit incorporates a locking screw which helps prevent unauthorised removal from the base. To fit, gently insert 
the device positioned so that the alignment mark on the rim is rotated slightly anti-clockwise relative to the 
alignment mark on the base. Rotate clockwise until the device drops in and the alignment marks meet. Tighten the 
locking screw, but do not over tighten. 
 
To remove the device, unscrew the retaining screw. The device should then be turned anti-clockwise allowing it to 
be removed from the base. 
 

 

Device Settings 

 

The sounder modes may be configured using the relevant panel software configuration package (OSP). 
 

 

Type 

Description 

Sound Pattern: 

SP0 

Sounder off 

 

 

 

 

 

 

SP1 

Single tone, 970 Hz continuous  

SP2 

Pulsed UK alert signal, 970 Hz 1s on, 1s off 

SP3 

Dual tone UK evacuate signal, 970 Hz 0.25s, 800 Hz 0.25s 

SP4 

This sound pattern is not supported in this product 

SP5 

Slow whoop up, 500 to 1200 Hz over 3s, 0.5s off 

SP6 

Sweep down, 1200 Hz to 500 Hz over 1s 

SP7 

Dual tone French warble, 550 Hz 0.1s, 440 Hz 400ms 

Sound Volume: 

L/M/H 

Low, medium and high settings are available 

See the Engineering & Commissioning Manual for your control panel (Sita, Duonet or Quadnet) for further details of how to 
program the above. 

 
 

Beacon Operation 

 

The unit includes a Visual Indication Beacon. This consists of a number of high output LEDs. 
 
The beacon will start to operate when  the device receives a command to activate its  sounder, even if the sound 
pattern is set to 

SP0 - Sounder off.

  If the beacon only is required to operate, Sound Pattern SP0 must be selected 

via the configuration software. 

 
Power Up 

 
The Sita Sounder/Strobe requires approximately one minute on power up to boot up its processor, charge for alarm 
operation and settle down to normal operation. Do not sound the alarms within the first minute after initializing the 
loop. 

 