26-0874 Issue 10
LED Indication:
Normal
50ms on / 20s interval
Fault
0.1ms on / 5s interval
Fire
50ms on / 400ms interval
IP Rating:
IP21C
System Compatibility:
MPS - Sita200plus V2.00 onwards.
MP - Sita200plus V2.30 onwards.
Duonet and Quadnet V1 onwards.
PRODUCT DESCRIPTION
VOLUME LEVEL (dBA)
@ 1m anechoic (Dual Tone)
Type
Product
Code
Name
Low
Medium
High
MP
205 0003
ASD Mk3
-
-
-
MPS
205 0001
ASD Mk3 with Sounder
65+
80
85
MPS
205 0012
ASD Mk3 with Sounder/Strobe
65+
80
85
LOOP CURRENT (mA)
Type
Product
Code
Name
Quiescent
SP0 - Off
Low
Medium
High
MP
205 0003
ASD Mk3
0.12
0.96
-
-
-
MPS
205 0001
ASD Mk3 with Sounder
0.12
0.99
1.48
4.03
5.84
MPS
205 0012
ASD Mk3 with Sounder/Strobe
0.12
3.99
4.48
7.03
8.84
BATTERY CURRENT (mA)
Type
Product
Code
Name
Quiescent
SP0 - Off
Low
Medium
High
MP
205 0003
ASD Mk3
0.12
2.00
-
-
-
MPS
205 0001
ASD Mk3 with Sounder
0.12
2.07
3.09
8.39
12.17
MPS
205 0012
ASD Mk3 with Sounder/Strobe
0.12
8.32
9.34
14.64
18.42
DLU RATING
Type
Product
Code
Name
SP0 - Off
Low
Medium
High
MP
205 0003
ASD Mk3
1
-
-
-
MPS
205 0001
ASD Mk3 with Sounder
1
1.5
4.5
6
MPS
205 0012
ASD Mk3 with Sounder/Strobe
4.5
5
8
10
N.B.
All specified volume and current readings, unless
otherwise stated are taken using sound pattern SP3.
Sita OSP versions prior to v4.06 and Quadnet/Duonet
OSP versions prior to v2.04 do not include all the above
DLUs.
0832
Fike Safety Technology Ltd
Unit 31, Springvale Ind. Est.
Torfaen, NP44 5BD
11
DoP-205-0001, DoP-205-0003, DoP-205-0012
EN54-3: 2001 +A1: 2002 +A2: 2006, EN54-5: 2000 +A1: 2002,
EN54-7: 2000 +A1: 2002 +A2: 2006, EN54-17: 2005, EN54-18: 2005
Sounder Technical Data: See 26-0747
Isolator Technical Data: See 26-1112
205-0001, 205-0003, 205-0012
Intended for use in the fire detection and fire alarm
Systems in and around buildings
Essential characteristics
Performance
Nominal activation conditions / Sensitivity, Response delay
(response time) and Performance under fire conditions
Pass
Operational reliability
Pass
Tolerance to supply voltage
Pass
Durability of operational reliability and response delay,
Temperature resistance
Pass
Durability of operational reliability, Vibration resistance
Pass
Durability of operational reliability, Humidity resistance
Pass
Durability of operational reliability, Corrosion resistance
Pass
Durability of operational reliability, Electrical stability
Pass
Performance under fire conditions
Pass
Durability of operational reliability, Resistance to ingress
Pass
Response delay (response time)
Pass
Technical Support
Contact your supplier for technical support on this
product.
Due to the complexity and inherent importance of a life
risk type system, training on this equipment is essential,
and commissioning should only be carried out by
competent persons. Fike cannot guarantee the operation
of any equipment unless all documented instructions are
complied with, without variation. This unit complies with
the EMC directive.
Fike’s policy is one of continual improvement and the right
to change a specification at any time without notice is
reserved. Whilst every care has been taken to ensure that
the contents of this document are correct at time of
publication, Fike shall be under no liability whatsoever in
respect of such contents. E&OE.