4.2.
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8
1
Protocol
Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Baud*
Specify baud rate
75, 150, 300 ,600, 1200, 2400,
9600
(Vendor limitation)
Parity*
Specify parity
Even
(Vendor limitation)
Data_Bits*
Specify data bits
8 (
Vendor limitation)
Stop_Bits*
Specify stop bits
1
(Vendor limitation)
Handshaking* Specify hardware handshaking
None
Poll_Delay*
Time between internal polls
0-32000 seconds,
0.05 seconds
Example
//
Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Poll_Delay
P8,
SCS-128,
9600,
Even,
None,
0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric
characters
Node_ID
SCS-128 station address of physical Server Node
1-127
Protocol
Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Connection
Specify which port the device is connected to the
FieldServer
P1-P8
1
SCS128_Ack*
If ON, Ack will be sent to Server upon receipt of every
indication response
OFF
,
ON
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Connection,
SCS128_Ack
NODE_A,
1,
SCS-128,
P8,
OFF
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction