SlotServer Configuration Manual
Page 35 of 37
ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.
For Technical Support call +1 661.716.5100
Appendix D.4.4.
Connections/ Adapters
Section Title
Connections
Column Title
Function
Legal Values
Port
Specifies the port through which the device is connected to the
FieldServer.
P1-P8, R1-R2
7
Baud*
Specifies Baud Rate
300,
9600
,
38400;
Parity*
Specifies serial data byte parity
Even,
Odd,
None
Data_Bits*
Sets number of data bits for serial port.
7,
8
;
Stop_Bits
Sets the stop bits for communications
1, 2
Line_Drive_Off
When using RS-485, specifies delay from end of message to when the RTS
line is deasserted
Time
in
seconds
Line_Drive_On
When using RS-485, specifies delay after RTS is asserted until message is
transmitted
Time
in
seconds
Ic_Timeout
Specifies inter-character timeout period within a message once it starts
Timeout
in
seconds
Turnaround_Delay
(Turnaround_Time)
This is the time the Server takes to initiate a response after having
received a poll.
Delay
in
seconds
Client/Server_Mode
Where two FieldServers are connected in Hot Standby mode each with a
PEX and a SCADA Tier, if the SCADA Tier of one FieldServer polls the
SCADA Tier of the other FieldServer, that tier will start acting as a Server.
Setting this parameter to Client_Only will prevent this happening.
Client_Only
Write_Queue_Mode*
Mode for dealing with potential accumulation of successive writes to the
same point can be configured.
Overwrite,
Blocking.
Write_Queue_Size*
The length of the queue can be configured if blocking mode is set.
Blocking will occur when there is no more space on the Write_Queue.
If size=0 every successive write is blocked. A message will be displayed
when blocking occurs, except if the Queue_Size=0.
Non-negative
integer,
0
Bias_Mode*
Only relevant to ProtoNode and X25. If this parameter is set to Yes or
Enabled, it loads the RS-485 line by placing additional resistance on it This
has the benefit of making the signals cleaner in a noisy environment but
may reduce the maximum number of devices possible in a multidrop
configuration.
Enabled, Yes,
Disabled
, No
Section Title
Adapter
Column Title
Function
Legal Values
Adapter
Adaptor name
Arcnet, DH+, , Profibus, etc..
MAC_Address (Net_number) Specify Network MAC address
Appendix D.4.5.
Nodes
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
(Device_Name)
Provides name for Node
Up to 32 Alpha
Numeric
Characters
Node_ID
Specifies Node ID Information
1-255
7
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.