Appendix C.
Vendor Information
Appendix C.1.
Installing SlotServer on a Remote Rack using CNB Cards
1
Appendix C.1.1.
Hardware and Software requirements
Two 1756 racks, one containing the CPU and the other the SlotServer
Two Controlnet CNB cards with connection cables to connect the racks to one other
RSlinx
RSLogix
RSNetworx
SlotServer EDS file (Available on SlotServer CD, or call Technical Support)
Appendix C.1.2.
Setup
Install the CPU and the first CNB card in the local rack.
Install the second CNB card and the SlotServer in the remote rack.
Connect the ControlNet Network
Power up the racks
Install the SlotServer EDS File using the RSLinx Hardware EDS Installation Tool.
Make sure the SlotServer has a valid configuration loaded. The default configuration shipped with the
SlotServer should suffice.
Refer to the SlotServer Configuration Manual for further information.
Note:
When configured in remote rack applications, the SlotServer does not support the use of EN2T-A cards, but
is compatible with EN2T-B cards.
1
The principles for connecting other 1756 bridging cards to the SlotServer are similar.