![FieldServer Omron FINS FS-8704-16 Driver Manual Download Page 10](http://html.mh-extra.com/html/fieldserver/omron-fins-fs-8704-16/omron-fins-fs-8704-16_driver-manual_2287906010.webp)
FS-8704-16 Omron FINS Manual
Page 7 of 37
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll_Free
: 888-509-1970
Example
// Data Arrays
Data_Arrays
Data_Array_Name,
Data_Format,
Data_Array_Length,
DA_CIO,
UInt16,
5143
DA_WR,
UInt16,
511
DA_HR,
Uint16,
511
DA_DM,
Uint16,
32767
1.06
Driver Specific FieldServer Parameters
Section Title
FieldServer
Column Title
Function
Legal Values
Title
Name for FieldServer
Text
System_Node_Id
Specify physical node Id on
network.
This is the last byte of the
IP Address of the
FieldServer. eg. If
FieldServer’s IP Address is
192.168.1.81 then this
parameter should be set to
81
1-126
Example
// FieldServer Driver specific parameters
FieldServer
Title,
System_Node_Id
Fins Client,
81
1.07
Client Side Connection Descriptors
Section Title
Adapter
Column Title
Function
Legal Values
Adapter
Adapter Name
N1, N2
2
Protocol
Specify protocol used
Fins, omn_fins or fins_udp
Udp_port_number Specify UDP port number
0,
9600 etc
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.