![FieldServer Modbus Daniels FS-8700-15 Driver Manual Download Page 6](http://html.mh-extra.com/html/fieldserver/modbus-daniels-fs-8700-15/modbus-daniels-fs-8700-15_driver-manual_2287904006.webp)
FS-8700-15 Modbus Daniels Manual
Page 4 of 7
device is connected to the
FieldServer
FS-X20 Serves: Serial Port
Protocol
Specify protocol used
Modbus_Daniels
Baud*
Specify baud rate
110 – 115200, standard baud
rates only,
9600
Parity* Specify
parity
Even, Odd,
None,
Mark,
Space
Data_Bits*
Specify data bits
7,
8
Stop_Bits*
Specify stop bits
1
Handshaking*
Specify hardware
handshaking
RTS, RTS/CTS,
None
Poll _Delay*
Time between internal polls
0-32000 seconds,
1 second
Example
//
Client Side Connections
Connections
Port,
Protocol,
Baud, Parity,
Handshaking,
Poll_Delay
P1,
Modbus_Daniels,
9600,
Even,
None,
0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric
characters
Node_ID
Modbus station address of
physical server node
1-255
Protocol
Specify protocol used
Modbus_Daniels
Connection
Specify which port the device is
connected to the FieldServer
FS-X40 Serves: P1-P8, R1-R2
FS-X20 Serves: Serial Port
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Connection
PLC 1,
1,
Modbus_Daniels,
P1
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll_Free
: 888-509-1970