FS-8700-132 Gamewell FCI-E3 Driver Manual
Page 18 of 20
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Message
Description
FCI_E3:#16 Err. Point Type='%c'(%#x) Not recognized. , drv_bd-
>point_identifier[0] , drv_bd->point_identifier[0] ) ;
FCI_E3:#17 Err. Loop=%d < 1. Rejected. , drv_bd->loop )
This message should only be printed if a byte
in a message has been corrupted. If you notice
it more than once then take a log and contact
tech support.
FCI_E3:#18 Err. Loop Type='%c'(%#x) Not recognized. , drv_bd-
>point_identifier[2] , drv_bd->point_identifier[2] )
If this error is repeated often it is possible that
a FCI firmware update has made the driver
unusable. Take a log and contact tech support.
FCI_E3:#19 Err. Relay=%d < 1. Rejected. , drv_bd->relay
This message should only be printed if a byte
in a message has been corrupted. If you notice
it more than once then take a log and contact
tech support.
FCI_E3:#20 Err. Zone=%d < 1. Rejected. , drv_bd->zone"
FCI_E3:#21 Err. Point Type not recognized
Valid Point Types are listed in section 5.3.2
5
FCI_E3:#22 Err. Undefined Point Type"
FCI_E3:#23 Err. Event Type not recognized
Valid Event Types are listed in section 5.3.2
5
FCI_E3:#24 Err. Undefined Event Type
FCI_E3:#25a Err. Length>99. Length Truncated
The maximum value for a sensor/module is 99.
The combination of address and length
specified produce a number > 99
5
FCI_E3:#25b Err. Length>99. Length Truncated
FCI_E3:#26 Err. Invalid Module number. Expected 1..99
Correct the configuration file
5
FCI_E3:#27a Err. Invalid Loop number. Expected 1..10
FCI_E3:#27b Err. Invalid Loop number. Expected 1..10
FCI_E3:#27c Err. Invalid Loop number. Expected 1..10
FCI_E3:#28 Err. Invalid Sensor number. Expected 1..99
FCI_E3:#29 Err. Invalid Zone number. Expected 1..255
FCI_E3:#30 Err. Invalid Relay number. Expected 1..255
FCI_E3:#31 Err. Point Type Invalid.
Valid Point Types are listed in Section 5.3.2
5
FCI_E3:#32 Err. No MD Length. Default to 1
The length of each Map Descriptor should be
specified. Refer to Section 5.3.2
5
FCI_E3:#33 Err. Driver can’t poll or write.
The driver can only listen passively for
message from the panel. Map Descriptors may
not be configured as active.
5
FCI_E3:#36 Err. Too Short. Bytes=%d , conn->ux_iptr"
An event message is less than 80 bytes long. If
this error is repeated often it is possible that a
FCI firmware update has made the driver
unusable. Take a log and contact tech support.
5
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.