FS-8704-07 Allen Bradley PCCC (TCP/IP) Driver Manual
Page 7 of 15
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
5.2
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Node_ID
Node ID of physical server node (PLC)
0-255
IP_Address*
IP address of physical server node (PLC). Must be on the
same subnet as the server or gateway
IP address e.g , 192.168.2.1,
-
Protocol
Specify protocol used
AB_CSP, AB_TCP
Adapter
Specify on which port the device is connected to the
FieldServer
N1
PLC_Type
Specify PLC Communications type.
PLC3, PLC5, SLC5
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol , PLC_Type , IP_Address
, Adapter
PLC_01
, 1
, AB_CSP
, SLC5
, 192.168.1.13 , N1