McQuay Micro Tech Open Protocol Driver Manual
Page 40 of 43
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Array Location Read/ Write/ Both Field Name
Number of Bytes Base Address Device Scaling Method
59
r
Oil Delta Pressure
1
0X040D
1
60
r
Oil Feed Temp.
1
0x0409
1
61
r
Oil Gage Pressure
1
0x0415
1
62
r
Oil Heater
1
0x0215
1
63
r
Oil Pressure Differential Switch
1
0X050E
1
64
r
Oil Pump
1
0X021D
1
65
r
Oil Sump Temp.
1
0X040A
1
67
r
Operating Hours
2
0x0430
1
68
r
Panel Rocker Switch
1
0X050E
1
69
r
Remote Amp Limit
1
0X043E
1
70
r
Remote Chilled Water Reset
1
0x0439
1
71
r
Remote Reset or Amp Limit Signal
1
0X040B
1
72
r
Remote Start/Stop Switch
1
0X050F
1
73
r
Soft Load Limit
1
0X043A
1
74
r
Starter Fault Switch
1
0X050F
1
75
r
Starter Transition Switch
1
0X050F
1
76
r
Superheat
1
0x0416
1
77
r
Surge Guard Switch
1
0X050E
1
78
r
Unit Status
1
0x0424
1
79
r
Unload Solenoid
1
0x0210
1
80
r
Vanes Closed Switch
1
0X050F
1
81
r
Watchdog Output
1
0x0214
1
82
b
Clear Current Fault
1
0X042A
1
83
b
Comm Port Baud Rate
1
0x0801
1
84
b
Correct Checksum
1
0x0800
1
85
b
Leaving Evaporator Temperature Setpoint
1
0x0900
7
86
b
Maximum Chilled Water Reset Setpoint
1
0x0820
9
87
b
Network Amp Reset
1
0x0450
1
88
b
Network Chilled Water Reset
1
0X044F
1
89
b
Network Start Stop
1
0x0451
1
90
b
Reset Option
1
0x0822
1
91
b
Soft Reset
1
0x0204
1
92
b
Start Mode
1
0x0824
1
93
b
Startup Differential Temp.
1
0x0826
9
94
b
Shutdown Differential Temp.
1
0x0827
9
Appendix C.5.4.
Equipment Type : 001ASC Air Cooled Screw Chiller
Array Location Read/ Write/ Both Field Name
Number of Bytes Base Address Device Scaling Method
8
1
r
Active Chilled Water Temperature Setpoint
1
0x045A
4
2
r
Ckt#1 Condenser Pressure
2
0x0467
2
4
r
Ckt#1 Alarm Conditions: Capacity
1
0x1F13
1
5
r
Ckt#1 Alarm Conditions: Condenser Pressure
2
0x1F09
2
7
r
Ckt#1 Alarm Conditions: Evap Leaving Water Temp 2
0x1F0F
1
9
r
Ckt#1 Alarm Conditions: Evap Pressure
2
0x1F07
2
11
r
Ckt#1 Alarm Conditions: Fan Stage
1
0x1F14
1
12
r
Ckt#1 Alarm Conditions: Liquid Line Temperature 2
0x1F0D
10
14
r
Ckt#1 Alarm Conditions: Outside Air Temp
2
0x1F11
10
16
r
Ckt#1 Alarm Conditions: Suction Temperature
2
0x1F0B
10
18
r
Ckt#1 Current Alarm
1
0x08B9
1
19
r
Ckt#1 Current Alarm HourMinuteMonthDateYear 1
0x1F02
1
8
See Appendix A.1.