CONFIGURING THE FIELDSERVER AS A SECUTRON MODUL-R DRIVER SERVER
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files provided with the FieldServer).
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Secutron Modul-R driver communications, the driver independent FieldServer buffers need to
be declared in the “Data Arrays” section, the FieldServer virtual node(s) need to be declared in the “Server Side
Nodes” section, and the data to be provided to the Client needs to be mapped in the “Server Side Map
Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
6.1
Server Side Connection Parameters
Section Title
Connections
Column
Title
Function
Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8
2
Baud*
Specify baud rate
150, 300, 1200, 2400, 4800,
9600
(Vendor
limitation)
Parity*
Specify parity
None
(Vendor limitation)
Data_Bits*
Specify data bits
8
(Vendor limitation)
Stop_Bits*
Specify stop bits
1
(Vendor limitation)
Protocol
Specify protocol used
Secutron
Example
//
Server Side Connections
Port , Protocol
, Baud , Parity
P1
, Secutron , 9600 , None
6.2
Server Side Node Parameters
Section Title
Nodes
Column Title Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric characters
Node_ID
Generic Node ID unique to port. Also used as panel number. 0-9
Protocol
Specify protocol used
Secutron
Port
Port to which node belongs
P1-P8
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.