Driver Version:
1.02
Document Revision: 2
A Sierra Monitor Company
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after March 2010
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-72 Secutron
Page 1: ... 1 02 Document Revision 2 A Sierra Monitor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after March 2010 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 72 Secutron ...
Page 2: ...ap Descriptor Parameters 8 5 3 1 FieldServer Specific Map Descriptor Parameters 8 5 3 2 Driver Specific Map Descriptor Parameters 8 5 3 3 Timing Parameters 8 5 3 4 Map Descriptor Example 9 6 Configuring the FieldServer as a Secutron Modul R driver Server 10 6 1 Server Side Connection Parameters 10 6 2 Server Side Node Parameters 10 6 3 Server Side Map Descriptors 11 6 3 1 FieldServer Specific Map ...
Page 3: ...h 1000 devices per circuit Each bit of the 32 bits in an unsigned quantity represents an alarm state 1 alarm 0 normal A set bit indicates an alarm and the clearing of a bit indicates the reset of an alarm A panel number is identified by the Node Id in the configuration files Panel circuit and device numbers range from 0 in messages e g Panel numbers 0 to 999 Circuit numbers 0 to 99 Device numbers ...
Page 4: ...alifornia 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 2 DRIVER SCOPE OF SUPPLY 2 1 Supplied by FieldServer Technologies for this driver FieldServer Technologies PART Description FS 8917 16 Pigtail cable for RJ45 Port ...
Page 5: ...ver com 3 HARDWARE CONNECTIONS The FieldServer is connected to the panels as shown below Configure the panels according to manufacturer s instructions SECUTRON PANEL FieldServer FieldServer Part 8917 16 Pigtail for RJ45 Port RJ45 Connect to one of the RS 232 Ports on the FieldServer P1 Brown Blue white Orange White 1 8 Connector Pinouts RJ 45 Pin From RJ 45 To Secutron 1 Brown Tx 8 White Orange Rx...
Page 6: ...age of the relevant data Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format BIT UInt16 Byte Data_Array_Length Number of Data Objects Must be larger than the data storage area required by the Map Descriptors for the data being place...
Page 7: ...er independent FieldServer buffers need to be declared in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value bein...
Page 8: ...iptor Parameters Column Title Function Legal Values Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Section 4 Data_Array_Offset Starting location in Data Array 0 to Data_Array_Length 1 as specified in Section 4 Function Function of Client Map Descriptor...
Page 9: ...lient Node_1 Device 90 100 P1C90_FUNCTION P1C90_FUNCTION 0 Passive_Client Node_1 Function 90 100 Any unique name Name will appear in Bridge Map Descriptor status information screens The rate at which the driver polls the panel A Data Array name must be one found under Data_Arrays Data from a circuit event will be stored in the array at Data_Array_Offset The Poller Data Array will contain non zero ...
Page 10: ...ient needs to be mapped in the Server Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value being the default 6 1 Server Side Connection Parameters Section Title Connections Column Title Function Legal Values Port Specify which port the device is connected to the FieldServer P1 P8 2 Baud Specify b...
Page 11: ...me Name of the Data Array where data is to be stored in the FieldServer One of the Data Array names from Data Array section above Data_Array_Offset Starting location in Data Array 0 to Data_Array_Length 1 as specified in Data_Array section Function Function of Client Map Descriptor Server Node_Name The name of the Node the Map Descriptor is attached to One of the Node Names specified in Server Nod...
Page 12: ...e Node_1 Device 90 100 P1C90_FUNCTION P1C90_FUNCTION 0 Passive Node_1 Function 90 100 Any unique name Name will appear in Bridge Map Descriptor status information screens The rate at which the driver polls the panel A Data Array name must be one found under Data_Arrays Data from a circuit event will be stored in the array at Data_Array_Offset Function may not be read or write since it implements a...
Page 13: ...rt fieldserver com Appendix A Troubleshooting Appendix A 1 Driver Messages Error Messages and Optional Map Descriptors The Client driver will report all events it receives from the panel on the RuiNet F screen If an event is received that has no corresponding Map Descriptor defined this will be reported on the RuiNet E screen This is a useful configuration tool to ensure that all required data is ...
Page 14: ...tron_Type device Secutron_Circuit 1 will set a bit and store the event function code A Decimal 65 at offset 3 in the Map Descriptors Data Array The Secutron_Type device Map Descriptors will set a bit if any of the events listed below occur on that circuit or zone The bit will be cleared if the panel reports the event as cleared The following table lists the full list of event function codes ASCII ...
Page 15: ... 2 Panel Circuit or Zone numbers The panel groups events under circuit or zone numbers When setting up a Client configuration it is necessary to create Map Descriptors to trap the events from the zones or circuits you want to see data from If an event is received that has no corresponding Map Descriptor defined this will be reported on the RuiNet E screen This is a useful configuration tool to ens...
Page 16: ... Data Array at the device offset values shown below Circuit Events Program Restart Circuit 69 000 Power On Hard reboot 003 Illegal Instruction 001 Watchdog 004 Unused Interrupt 002 Clock Monitor 005 Orphan Interrupt Hot Key Activation Circuit 90 Function number of the Hot Key pressed 001 Fire Drill 026 Switch 11 On 002 Lamp Test 027 Switch 12 On 003 Releaser Disconnect 028 Switch 13 On 004 Relay d...