FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 8 of 21
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll Free
: (888) 509-1970
Parameter
Addresses
For each SLC loop per Node
Memory Type :
Detector ; Module
Fire Alarm
1 – 159
Security Life
160 – 318
Life Critical
319 – 477
Medical Emergency
478 – 636
Security Alarm
637 – 795
Critical Process
796 – 954
Supervisory
955 - 1113
Disabled
1114 – 1272
Prealarm
1273 – 1431
Active
1432 – 1590
ON/OFF
1591 – 1749
Memory Type :
Detector_Trouble; Module_Trouble
Troubles/Faults
1 – 159
Parameter
Addresses
For each Node
Memory Type :
Node_Trouble
Troubles/Faults
1 – 508
Memory Type :
Panel
Panel
(Maximum12 Boards and 8 Panel circuits per Board )
Hardware address memory address
Board 1 panel 1 1
Board 1 panel 2 2
Board 2 panel 1 9
-----
-----
Board 12 panel 8 96
)
Fire Alarm
1 – 96
Security Life
97 - 192
Life Critical
193 - 288
Medical Emergency
289 - 384
Security Alarm
385 - 480
Critical Process
481 - 576
Supervisory
577 - 672
Disabled
673 - 768
Prealarm
769 - 864
Active
865 - 960
ON/OFF
961 - 1056
Memory Type :
Panel_Trouble
Troubles/Faults
1–96
Memory Type :
Bell_Trouble
Troubles/Faults
1-4
Table 1 – Memory Mapping Address Structure.