FS-8700-49_Data_Aire_DAP
Page 43 of 48
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.FieldServer.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll_Free
: 888-509-1970
Byte Bit
Relative
Offset
Location in
Data Array
(Absolute
Offset) Each
alarm stored as
a separate bit
Location in Data
Array (Absolute
Offset) Each set
of 8 alarms
stored as a
byte*
046, 048 and 049 Units
DAP 80 Units
3
0
24
97
46:00
Low air temperature
warning
Local alarm #1: See
tag inside door
3
1
25
98
46:01
High air temperature
warning
Local alarm #2: See
tag inside door
3
2
26
99
46:02
Low Humidity warning
Local alarm #3: See
tag inside door
3
3
27
100
46:03
High Humidity warning
Local alarm #4: See
tag inside door
3
4
28
101
46:04
Low chilled-water-in alarm
Standby pump on:
check primary pump
3
5
29
102
46:05
High chilled-water-in
alarm
UPS power on:
check main power
supply
3
6
30
103
46:06
Low chilled-water-out
alarm
Custom message on
optional input #1
3
7
31
104
46:07
High chilled-water-out
alarm
Custom message on
optional input #2
4
0
32
105
47:00
High or Low limits
misadjusted
Custom message on
optional input #3
4
1
33
106
47:01
Air temperature sensor
error
Custom message on
optional input #4
4
2
34
107
47:02
Humidity sensor error
Humidification
Inhibited
4
3
35
108
47:03
Discharge air sensor error Reheat inhibited
4
4
36
109
47:04
No communications with
temp/humid module
Reheat and
humidification
inhibited
4
5
37
110
47:05
No communications with
LCD module
Discharge air
temperature limit
(just a condition)
4
6
38
111
47:06
Alarm network
communications failure
Reheat mode during
dehumidification
(just a condition)
4
7
39
112
47:07
AC Power or controller
restart
Manual Override:
Check bypass
switches (DAPII ver
5.1 and later)
5
0
40
113
48:00
Network doppelganger
error
N/A
5
1
41
114
48:01
Incompatible Fahrenheit /
centigrade mode
N/A
5
2
42
115
48:02
Schedule normal
maintenance due
N/A
5
3
43
116
48:03
compressor short cycle
warning
N/A
5
4
44
117
48:04
Fan motor overload,
check motor amperage
N/A