4.5

 

Client Side Map Descriptors 

4.5.1

 

FieldServer Related Map Descriptor Parameters  

Column Title 

Function 

Legal Values 

Map_Descriptor_Name  Name of this Map Descriptor 

Up to 32 alphanumeric characters 

Data_Array_Name 

Name of Data Array where data is to be 
stored in the FieldServer 

One  of  the  Data  Array  names  from  “Data 
Array” section above 

Data_Array_Offset 

Starting location in Data Array 

0  to  (Data_Array_Length-1)  as  specified  in 
“Data_Array” section 

Function 

Function of Client Map Descriptor 

Rdbc, Wrbc 

4.5.2

 

Driver Related Map Descriptor Parameters  

Column Title 

Function 

Legal Values 

Node_Name 

Name  of  Node  to  fetch  data 
from 

One  of  the  node  names  specified  in  “Client  Node 
Descriptor” above 

Profibus_Data_Type  Arrangement of buffer data 

Byte, Word, Bool, Float 

Address 

Starting  address  of  buffer  in 
bytes 

0 - 243 

Length 

Length of Map Descriptor

3

 

1 - 244 ( BYTE ) 
1 - 122 ( WORD ) 
1 - 1952 ( BOOL ) 
1 - 61 ( FLOAT ) 

4.5.3

 

Timing Parameters 

Column Title 

Function 

Legal Values 

Scan_Interval 

Rate  at  which  data  is  transferred  from  FieldServer  data  arrays  to  Profibus 
Master buffers. 

≥0.001s 

                                                                 

3

 A maximum combined total length of 1536 bytes are permitted for all Map Descriptors accessing Slave devices. 

Summary of Contents for A Sierra Monitor Company FS-8700-122

Page 1: ...cument Revision 3 A Sierra Monitor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after August 2011 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 122 X30 Profibus DP Master ...

Page 2: ...ration 3 3 Hardware Connections 4 3 1 Hardware Connection Tips Hints 4 4 Configuring the FieldServer as a X30 Profibus DP Master Client 6 4 1 FieldServer 6 4 2 Data Arrays Descriptors 6 4 3 Client Side Connection Descriptors 7 4 4 Client Side Node Descriptors 7 4 5 Client Side Map Descriptors 8 4 5 1 FieldServer Related Map Descriptor Parameters 8 4 5 2 Driver Related Map Descriptor Parameters 8 4...

Page 3: ...s Supported FieldServer Mode Nodes Comments Client DPV1 MASTER CLASS 1 ONLY 125 This is the maximum number of Profibus DP Slaves that can be connected to the FieldServer A maximum total of 1536 bytes can be transferred with all DP Slaves 2 DRIVER SCOPE OF SUPPLY 2 1 Supplied by FieldServer Technologies for this driver FieldServer Technologies PART Description 52201 Profibus Connector FS 8915 31 Ad...

Page 4: ...iption Housing Shield Connected to PE 1 Not connected 2 Not connected 3 B Line Positive RxD TxD according to RS 485 specification 4 RTS 1 Request to Send 5 GND BUS 2 Isolated GND from RS 485 side 6 5V BUS 2 Isolated 5V from RS 485 side 7 Not connected 8 A Line Negative RxD TxD according to RS 485 specification 9 Not connected Only A line B line and Shield are used for most applications Profibus Ne...

Page 5: ...ourt Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com Use the recommended network cable and terminators as specified by the Profibus network organization and or the manufacturer of the network equipment ...

Page 6: ... in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value being the default 4 1 FieldServer Section Title FieldServe...

Page 7: ...ctions Column Title Function Legal Values Adapter Adapter Name Prof_DP Example Client Side Connections Adapters Adapter Prof_DP 4 4 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Station address of physical remote Profibus Slave 0 125 Protocol Specify Protocol used Prof_Master Example Clie...

Page 8: ...ng location in Data Array 0 to Data_Array_Length 1 as specified in Data_Array section Function Function of Client Map Descriptor Rdbc Wrbc 4 5 2 Driver Related Map Descriptor Parameters Column Title Function Legal Values Node_Name Name of Node to fetch data from One of the node names specified in Client Node Descriptor above Profibus_Data_Type Arrangement of buffer data Byte Word Bool Float Addres...

Page 9: ...example demonstrates the transfer of I O data with Remote Profibus DP Slaves using Station Addresses of 1 and 125 Map Descriptor Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Profibus_Data_Type Address Length Scan_Interval Word_In_003 Word_Input 0 Rdbc PDP_SLV003 Word 0 50 1s Word_Out_003 Word_Output 0 Wrbc PDP_SLV003 Word 0 50 1s Byte_In_125 Byte_Input 0 Rdbc PDP_SLV125...

Page 10: ... serial RS 232 cable from the PC with the tool installed to the serial connector on the X30 as shown in Section 3 Expand the Profibus Master Tree select the ABM DPV device and drag it onto the Bus Configuration Screen This is the X30 FieldServer Profibus DP Master device Select Project New Expand the Profibus Master Tree select the ABM DPV device and drag it onto the Bus Configuration Screen This ...

Page 11: ... 1970 email support fieldserver com Right click on the Profibus Slave and assign its Profibus address Continue adding all other Slaves and setting their Profibus addresses Right click on the ABM DPV Master device and select Object Properties Set the Master Station Address to the same as the System_Station_Address used in the FieldServer s config csv file Also set the desired Profibus Network Baud ...

Page 12: ...r them as well Important Note Changing of Input and Output Addresses are not allowed All addresses must be contiguous for the X30 Profibus to work correctly Select Online Driver selection and on the serial Tab choose the serial port on the PC connected to the X30 by clicking on Configure Configure path Ensure that the X30 FieldServer is running and that a matching configuration file with Node and ...

Page 13: ... USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com Choose Online Download configuration to install the embedded database in the X30 Important Note Note that the X30 must be running with a valid configuration file before it will allow download of a new database ...

Page 14: ... selected in the configure path setting Ensure that the X30 is powered up with a valid configuration file declaring all the Slaves to be communicated with Confirm that the Run Led is flashing The following message on the E screen of Ruinet is shown when the X30 detects a request for new database download Detected New Profibus Database Restarting FieldServer in 10 seconds Appendix A 1 2 A Configura...

Reviews: