background image

11

16

12

17

13

18

14

19

15

20

What is Superheat and Subcooling?

Why Do I Need to Measure It?

Superheat is the difference between the 

actual temperature of the refrigerant (gas) as 

it leaves the evaporator and the boiling point 

of the refrigerant. After boiling, the refrigerant 

continues to heat up. The number of degrees it 

“heats up” after boiling is called the superheat. 

Under worst case conditions (low load for fixed 

orifice systems), the refrigerant in the evaporator 

boils off near the end of the evaporator coil. To 

make sure liquid doesn’t enter the compressor 

under the worst case condition (low load), 

the refrigerator or A/C manufacturers publish 

charts indicating what the superheat should be 

at a given indoor wet bulb measurement and 

outdoor air temperature.

Measuring superheat is your best indication 

on a fixed orifice system of the proper 

refrigerant charge and operating conditions. 

If everything else is working properly and the 

actual superheat is too high, add refrigerant. If 

it’s too low, evacuate refrigerant. 

Subcooling is the difference between the 

boiling point of the refrigerant in the condenser 

and the actual temperature of the refrigerant 

as it leaves the condenser. The degrees that the 

refrigerant “cools down” below the boiling point 

is the subcooling. Under worst case scenario 

(low load for TXV) the subcooling will continue 

to rise. If the subcooling rises too high, liquid 

may be backed into the compressor causing 

damage and catastrophic failure. See www.

fieldpiece.com for more technical articles. 

 

Location of Subcooling Test

  Location of Superheat Test

Specifications

Display size: 

5 inches (diagonal)

Backlight: 

Blue (On for 3 minute unless turned off manually)

Mini-USB Port:

  For updating to latest version of firmware.

Battery:  

6 x AA (Battery life below based on alkaline type)

Battery life:

  350 hours (without backlight)

Low battery indication:

 

  is displayed when the battery 

voltage drops below the operating level

Auto Shut off:  

30 minutes of inactivity when APO is activated

Operating environment:

 32°F to 122°F (0°C to 50°C) at <75% 

relative humidity

Storage temperature:

 -4°F to 140°F (-20°C to 60°C), 0 to 80% RH 

(with battery removed)

Temperature coefficient:

  0.1 x (specified accuracy) per °C (0°C to 

18°C, 28°C to 50°C), per 0.6°F (32°F to 64°F, 82°F to 122°F)

Over range:  

"OL" or "-OL" is displayed

Weight: 

3.04 lbs (1.38 kg)

Pressure

Connector Type: 

 Standard 1/4" NPT male flare fitting

Range:

  29” HgV to 580 Psig (English), 74 cmHgV to 0 to 4000KPa 

(Metric)

Resolution:

 0.1 psi/inHg; 1 kPa/cmHg

Accuracy:

  29” HgV to 0” HgV: ±0.2” HgV

74 cmHgV to 0 cmHgV: ±1 cmHgV

0 to 200 Psig: ±1 Psi; 0 to 1378 KPa: ±7 KPa; 0 to 1.378MPa: 

±0.007MPa; 0 to 13.78 bar ±0.07 bar

200 to 580 Psig: ±(0.3% of 1 Psig); 1378 to 4000KPa: ±(0.3% of 

7 Kpa); 1.378 to 4.000MPa: ±(0.3% of 0.007MPa); 

13.78 to 40.00bar: ±(0.3% of r0.07bar)

Maximum overload pressure:

 800 psig

Units:

 Psig, kPa, MPa, bar, inHg, and cmHg

Temperature

Sensor type: 

 Type K thermocouple

Range: 

-95°F to 999.9°F (-70°C to 537.0°C)

Resolution:

 0.1°F/°C

Accuracy: 

±(1.0°F) -95°F to 199.9°F; ±(0.5°C) -70°C to 93°C 

±(2.0°F) 200°F to 999.9°F; ±(1.0°C) 93°C to 537.0°C 

Note: All accuracies are after a field calibration.

Recommended 

Accessory

Easy View Micron Gauge

Model SVG3

Measure the depth of the vacuum in microns 

of mercury to verify all moisture and non-

condensibles have been removed from the 

system. For the most accurate reading, connect 

directly to a service port on the system or to a 

Schrader core removal tool (illustrated below).

Calibration

Temperature 

To calibrate your SMAN temperature 

thermocouples, adjust the pot on the front 

of the meter labeled SLT Cal or LLT Cal. The 

best way to calibrate is to match to a known 

temperature. Ice water is very close to 32°F and 

is readily available. Accuracies of one degree or 

better are easily obtained.

1   Stabilize a large cup of ice water by stirring. Pure, distilled water 

will be the most accurate.

2   Immerse the temp probe in ice water from SLT and adjust the 

SLT Cal pot with a flathead screwdriver and let it stabilize, keep 

stirring.

3   Repeat Step 3 for temp probe in LLT.

Pressure Zeroing

To calibrate your SMAN340 pressure sensors 

to atmospheric pressure, ensure that your 

SMAN340 is disconnected from any pressure 

source and at equilibrium with the ambient 

pressure. 

1  Press the CAL Atmospheric Pressure button and your SMAN340 

will set the zero point of pressure to the ambient pressure.

Advanced Pressure Calibration

Your SMAN340 has the ability to perform a 

linear adjustment of the pressure sensors based 

on refrigerant type, temperature, and pressure.

Calibration setup:

  For best results, first perform both the 

Temperature and Pressure Zeroing procedures. See Calibration 

section for details. This will ensure pressure readings are zeroed 

and thermocouple is properly calibrated to the SLT port of the 

SMAN. Calibration to LLT port is not necessary for this calibration. 

The refrigerant cylinder should be stored in a stable ambient 

environment for at least 24 hours before calibration.  

1   Plug in a Type K thermocouple into SLT. (A bead type 

thermocouple, like the ATB1, is recommended.)

2  Connect the SMAN340 to a refrigerant cylinder of a known, 

single refrigerant using an EPA approved service hose. Be sure 

to open both HIGH and LOW side valves on your manifold and 

cap the unused ports. (If caps are not available you can connect 

both ends of a refrigerant hose to the two unused caps. Note: 

Some refrigerant will remain in the hoses which will need to be 

recovered.)

3   Press the REFRIGERANT button to match the refrigerant of the 

cylinder you are using.

4   Attach bead-type thermocouple to the side of the cylinder using 

tape. It is recommended to attach in the middle of the cylinder. 

Important:  Let the temperature of the thermocouple stabilize to 

the refrigerant temperature for 1 to 2 minutes or until stable. 

5   Open the refrigerant cylinder. The pressure inside cylinder should 

now be displayed on both HIGH and LOW side pressure sensors.

6   Press the CAL Test Pressure button. If successful, "Good" will 

display for 3 seconds. If failed, "Err" will display for same time.

Your SMAN checks with its built-in P-T charts to compare the 

temperature of the refrigerant in the tank to the vapor saturation 

temperature based on the refrigerant you selected. If the measured 

pressures on your SMAN are within ±3psi of the P-T chart pressure 

corresponding to the vapor saturation temperature, the SMAN will 

adjust the pressure sensor linearity to match the P-T chart.

Possible causes of failed "Err" pressure calibration:

1. Refrigerant tank was not stored in stable ambient conditions for at 

least 24 hours.

2. Thermocouple attached to refrigerant tank was not properly 

calibrated to SLT port of SMAN.

3. Thermocouple was plugged into wrong port LLT instead of SLT.

4. Incorrect refrigerant was selected on the SMAN.

Limited Warranty

This meter is warranted against defects 

in material or workmanship for one year 

from date of purchase from an authorized 

Fieldpiece dealer. Fieldpiece will replace or 

repair the defective unit, at its option, subject 

to verification of the defect.

This warranty does not apply to defects 

resulting from abuse, neglect, accident, 

unauthorized repair, alteration, or unreasonable 

use of the instrument.

Any implied warranties arising from the sale of 

a Fieldpiece product, including but not limited 

to implied warranties of merchantability and 

fitness for a particular purpose, are limited to 

the above. Fieldpiece shall not be liable for loss 

of use of the instrument or other incidental or 

consequential damages, expenses, or economic 

loss, or for any claim of such damage, expenses, 

or economic loss. 

State laws vary. The above limitations or 

exclusions may not apply to you.

Obtaining Service

Email Fieldpiece warranty department at 

[email protected] for current fixed 

price repair service. Send check or money 

order made out to Fieldpiece Instruments for 

the amount quoted. If your meter is under 

warranty there will be no cost for the repair/

replacement. Send your meter, freight prepaid, 

to Fieldpiece Instruments. Send proof of date 

and location of purchase for in-warranty service. 

The meter will be repaired or replaced, at the 

option of Fieldpiece, and returned via least cost 

transportation.

For international customers, warranty for 

products purchased outside of the U.S. should 

be handled through local distributors. Visit our 

website to find your local distributor.

High Side

Low Side

TXV

Compressor

Direction of

Refrigerant

Flow

Condenser

Evaporator

!

  WARNINGS

DO NOT APPLY MORE THAN 800 PSI TO ANY PORT ON THE MANIFOLD.

FOLLOW ALL EQUIPMENT MANUFACTURER'S TESTING PROCEDURES 

ABOVE THOSE IN THIS MANUAL IN REGARDS TO PROPERLY 

SERVICING THEIR EQUIPMENT.

Directly to 

Service Port

Schrader Core 

Removal Tool

Hose

To

Pump

MICRONS OF MERCURY

S

CUUM

U E

MIN

ALARM

ENTER

Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176

TestEquipmentDepot.com 

Reviews: