Quick Start

1  Install six AA batteries into rear battery com-

partment. Batteries included in packaging.

2  Press the center blue button for 1 second to 

turn on your new manifold.

3  Connect hoses and pipe clamps  to the mani-

fold and the system.

4   See real-time pressure and temperature mea-

surements all at once!

Certifications

  

C-Tick (N22675)

  

CE

 

 

RoHS Compliant

Description

Your SMAN340 is a superb two-valve Digital 

Manifold for HVACR professionals. See all your 

pressures and temperatures at the same time 

on the redesigned large display with bright 

blue backlight. 

SMAN340 combines high precision, absolute 

pressure sensors, a superheat/subcooling 

calculator, and dual temperature measurements. 

Your SMAN340 calculates and displays target 

superheat and actual superheat to verify proper 

charge.  

SMAN340 is designed to meet the demands 

of HVACR field service with a rugged rubber 

boot for durability, a strong metal hanger for 

easy storage and a form fitting, water resistant, 

padded nylon pouch. SMAN340 has a very 

intuitive user interface and long battery life.

Your SMAN comes pre-programmed with 

accurate P-T charts for 45 of the most common 

refrigerants in the field so you are always 

prepared for any job.

     

Fieldpiece

Digital Manifold

OPERATOR'S MANUAL

Model SMAN340

 

Controls

 

1  Insert Type K thermocouple plugs here.

2  Temperature calibration pots.

3  Press to zero atmospheric pressure.

4  Press to calibrate to refrigerant tank.  

(See Advanced Pressure Calibration section.)

5  Press to confirm selection.

6  Press/hold to cycle through refrigerants.

7  Press to enter Target Superheat mode.

8  Press to scroll up/down to adjust values.

9  Press to adjust units. 

10 Hold 1 second to power on or off. Press to toggle backlight.

11 Turn clockwise to close High side port.

12 Turn clockwise to close Low side port. 

Functions

Superheat and Subcooling

Your SMAN340 can calculate and display both superheat and 

subcooling simultaneously. 

1   Select the appropriate refrigerant using the REFRIGERANT button.

2   Connect EPA approved refrigerant hoses to low and high side on 

SMAN340. Plug Type K thermocouple pipe clamps to SLT and LLT. 

3   Connect your SMAN340 to the system:

 

Superheat: 

 Hand tighten low side hose to suction line service 

port. Place the SLT pipe clamp thermocouple on the suction line  

between the evaporator and compressor, no closer than 6 inches 

to compressor. 

 

Subcooling:

  Hand tighten high side hose to liquid line service 

port. Attach the LLT pipe clamp thermocouple on the liquid line 

between the condenser and expansion valve (TXV), as close to the 

service port as possible.

4   After turning the system on or making any adjustments to 

the system wait 15 minutes before charging by superheat or 

subcooling to ensure the system is stabilized. 

5  To add or remove refrigerant connect a refrigerant or recovery 

tank to the center port on SMAN340. Follow charging or recovery 

practices from manufacturer. Use the low side and high side 

valves on SMAN340 to charge or recover refrigerant as needed. Let 

system stabilize again for 15 minutes.

Note:  When superheat and/or subcooling cannot be calculated an 

"OL" or "-OL" will be displayed. Please check the following:

1  The correct refrigerant is selected on the SMAN.

2  The pipe thermocouples are plugged into SLT/LLT ports and are in 

good working condition.

3  The pipe thermocouples are attached in the appropriate location on 

the system. See step 3 above for details.

Target Superheat

 Target Superheat is useful for charging fixed orifice air conditioning 

Target Superheat is useful for charging fixed orifice air conditioning 

systems. Your SMAN will calculate the target superheat for you. Just  

manually input the IDWB (indoor wet bulb) and ODDB (outdoor dry 

bulb) temperatures into the SMAN.

Input IDWB and ODDB manually

1  Press Target SH button to enter Target SH mode. IDWB will begin 

blinking indicating it is ready for an input.

2  Press UP or DOWN ARROW to toggle between IDWB or ODDB 

input. Hold ENTER to select which temperature you want to input 

first, either IDWB or ODDB. The far left digit of IDWB or ODDB will 

begin blinking indicating manual input mode is ready. 

3  Press the UP or DOWN ARROW to change values and press ENTER 

to lock in each digit. Once the last digit for ODDB or IDWB is locked 

in, the calculated target superheat will show in the center column 

of the display. A solid HOLD will display to the left of the TSH 

calculation indicating a static target superheat calculation.

Note:  If the inputted temperature is out of the calculable range for IDWB 

or ODDB an "Err" will flash once and a double beep will sound. IDWB 

range (40°F to 125°F, 4.4°C to 51.7°C) and ODDB range (50°F to 

140°F, 10°C to 60°C). Re-input a temperature within these ranges to 

calculate target superheat. 

Changing Units

Your SMAN can display pressure and temperature measurements in 

English, Metric or combination of both units.

1  Press UNITS to enter unit selection screen.

2  Use ARROW to select your desired pressure units. Press ENTER.

3  Use ARROW to select your desired temperature units. Press ENTER 

to return to pressure units.

4  Press UNITS to return to normal SMAN display.

Refrigerants

The P-T charts of the following 45 refrigerants come pre-

programmed into your SMAN. In your SMAN the refrigerants are listed 

in order of most commonly used. Here, they are listed in numerical 

order for easy reference.

R11, R113, R114, R12, R123, R1234YF, R124, R125, R13, R134A, R22, 

R23, R32, R401A(MP39), R401B, R402A, R402B, R404A, R406A, R407A, 

R407C, R407F, R408A, R409A, R410A, R414B (Hotshot), R416A, R417A, 

R417C (HOT SHOT 2), R420A, R421A, R421B, R422A, R422B(NU22B), 

R422C(Oneshot), R422D, R424A,  R427A, R434A(RS-45), R438A(MO99), 
R500, R502, R503, R507A, R508B  (Suva95)

Using Different Refrigerants

You can use your manifold with different refrigerants. Be sure to 

purge your manifold and hoses before connecting to a system with a 

different refrigerant.

Firmware Updates

Your SMAN340 firmware can be updated in the field to ensure you 

always have the most up-to-date features for your manifold. Just go 

to www.fieldpiece.com to periodically check for the latest firmware 

version. If a newer version is available, follow the download link and 

installation instructions on the website. Connect your SMAN340 to the 

PC via a mini-USB to USB cable (not included) to install the update on 

your SMAN.

To check your current firmware version, power off your SMAN340. 

Press and hold the blue power button for about 6 seconds. The SMAN340 

firmware version will show in the top right corner of the display (X.XX).

Maintenance

Clean the exterior with a dry cloth.  Do not 

use liquid.

Battery Replacement

The battery must be replaced when the 

battery life indicator 

 is empty. SMAN will 

display "lo batt" and power off. Remove rear 

battery cover and replace with 6 AA batteries.

Auto Power Off (APO)

To conserve battery life, your SMAN will 

power down after 30 minutes of inactivity. APO 

is activated by default and APO displays above 

the battery icon. To deactivate, press and hold 

ENTER while powering on the SMAN. When 

deactivated, APO will no longer show above 

the battery icon.

LOW

HIGH

   

Pressure (bar)

   

Pressure (pounds/in

2

)

    Pressure (kilopascals or Megapascals)

   

Negative Pressure (inches of mercury)

    Negative Pressure (cm of mercury)

  

Suction Line Temperature

   

Liquid Line Temperature

    Vapor Saturation Temperature

    Liquid Saturation Temperature

    

Superheat

    

Subcooling

  

Target Superheat

 

Static Target Superheat Calculation

   Outdoor Dry Bulb

    Indoor Wet Bulb

   

Battery Life       

   

Auto Power Off Enabled

   

Selected Refrigerant of System

13

11

12

1

1

2

2

3

4

5

8

9

10

6

7

LOW

HIGH

 