Phase Rotation Test (L1L2, L1L3)

Connect 3-phase power lines in the correct order to the terminals of 

a motor to ensure the motor turns in the intended direction. Incorrect 

wiring can damage some equipment. The terminals on the motor are 

usually marked L1, L2, and L3; however, the wires supplying power 

usually are not. Perform a simple phase rotation test with two test leads 

to quickly identify the order of 3-phase power lines.

Range:

  80±5 VAC to 600VAC (50Hz to 80Hz)  

Resolution:  

0.1V

Accuracy:  

±(1.5% rdg + 10 dgts)

Overload Protection:

  600VDC or AC rms

How to Perform a Phase Rotation Test

Set 1:  Select Function

Switch to 

. Plug black test lead 

into the COM (L1) port and red test lead 

to the VΩ (L2 L3) port on the SC680. 

You will see “L1L2” blinking 

to indicate phase rotation test 

is ready to begin.

Step 2:  Connect Leads

Connect both black and red 

test leads to any two of the three 

phase voltage lines in question. 

The line voltage will hold on the 

bottom display. Blinking L1 and 

L2 disappear. L3 will blink on top 

display to indicate test is ready for 

Step 2.

Important:  Step 2 must 

be performed within 
5 seconds of complet-
ing Step 1 or “Err” will 
show and Step 1 must 
be repeated.

Step 3:  Move Red Lead

With the black lead still on 

“L1”, move the red test lead to the 

third 3-phase voltage line. The line 

voltage will hold on the bottom 

display. The top display will show 

L123 indicating forward or L321 

indicating reversed.

Simply swap any two lines to 

change the direction. You can verify 

this by performing the test again.

Summary of Contents for SC680

Page 1: ...1 Fieldpiece Job Link System Power Clamp Meter OPERATOR S MANUAL Model SC680 INR USH ...

Page 2: ...erated from frequencies above 1000Hz as the low pass filter limits voltage measurements to below 1000Hz Do not use during electrical storms or in wet weather Do not use around explosive gas dust or vapor Do not apply more than the rated voltage to as marked on the meter between terminals or between any terminal and earth ground Donotusewithoutthebatteryandthebackcase properly installed Replace bat...

Page 3: ...e proper operation Usetheproperterminals functionsandrangefor your measurements Never ground yourself when taking electrical measurements Connect the black common lead to ground or neutral before applying the red test lead to potential voltage Disconnect the red test lead from the voltage first Always work with a partner Keep fingers behind the finger guards on the probes All voltage tests All vol...

Page 4: ...amperagereadingsnomatterhowyou clamp around a wire with the swivel head AAC clamp Verify the order of 3 phase voltage lines with just two leads Capture L1 L2 and L1 L3 to check that motor lines are correctly installed with Phase Rotation test TakemoreaccurateVACandAACreadingsonvariable frequency drives with True RMS sensing technology Measure the starting amp draw of a compressor with Inrush curre...

Page 5: ...autoranging and select the range manually Cycle through displayed values on applicable switch positions Press for 1 second to toggle F and C TRUE RMS AUTO OFF TYPE K 30V MAX T1 L1 L2 L3 T2 Sync OFF Range Select H M m SC660 ZERO ADC F C TEMP CAT III 600V COM USH TRUE RMS AUTO OFF TYPE K 30V MAX T1 T2 S y n c OFF Range Select H M m SC660 Z E R O A D C F C INRUSH TRUE RMS AUTO OFF TYPE K 30V MAX T1 L...

Page 6: ...t Celsius ContinuityTest DiodeTest Frequency Hertz Duty Cycle percentage ResistanceTest Ohms CapacitanceTest farads Microamps DC Nano Unit 10 9 one billionth Micro Unit 10 6 one millionth Milli Unit 10 3 one thousandth Kilo Unit 103 one thousand Mega Unit 106 one million Alternating Current Direct Current Easy to Read Display Easily see your measurements on the large dual display You ll never miss...

Page 7: ...sure DC voltages on circuit boards on more advanced HVACR systems and logic control boards InVDC ADC dial position VDC is shown on lower display Press SELECT button to show ADC on the top display at the same time Ranges 1000mV 10V 100V 1000V Resolution 0 1mV Accuracy 0 5 5 Input Impedance 5MΩ Overload Protection 1000VDC or 750VAC rms Non ContactVoltage NCV Use NCV to check 24VAC from a thermostat ...

Page 8: ...lect H M m SC660 ZE RO ADC F C TEMP CAT III 600V COM INRUSH for 1 second to zero the ADC value in the top display Ranges 100A 600A Resolution 0 01A Jaw Opening 1 2in 30 mm Accuracy 2 5 15 100A 2 0 10 600A Overload Protection 600ADC Amps AC AAC Frequency Hz through the clamp and Inrush AAC current is measured in theVAC 100AAC Hz orVAC 600AAC Hz switch position shown above Inrush AAC Current Inrush ...

Page 9: ...000kHz Resolution 0 01Hz Accuracy 0 1 5 Sensitivity 10Hz to 1000kHz 3 5Vrms Minimum PW 1µs Duty Cycle Limits 30 and 70 Overload Protection 600VDC or 600VAC rms Duty Cycle Dutycycleshowsthe OnTimeofa5Vlogicsignalsquarewave Ranges 5 95 40Hz to 1kHz 10 90 1kHz to 10kHz 20 80 10kHz to 20kHz Accuracy 5V logic 2 10 Resolution 0 1 PulseWidth 10µs Overload Protection 600VDC or 600VAC rms Capacitance MFD T...

Page 10: ...erfect for checking isolated fuses use the continuity function to test whether a circuit is open no beep no green LED or closed beep and green LED Press SELECT once to enter Continuity mode Range 100Ω Resolution 0 01Ω Response time 100ms Audible beep 30Ω Visual Indicator Green LED Overload Protection 600VDC or 600VAC rms DiodeTest O O F F F F MFD NCV V AC VDC AAC Hz Hz C AUTO OFF RUE RMS CAT III 6...

Page 11: ...Unplug Leads and Slide TEMP Switch to the Right COM Temperature Calibration Thermocouples T C are not calibrated directly Instead eachT C jack T1 andT2 must be calibrated to the particularT C that is plugged into it Though it s possible for a calibration to hold for years it s best practice to calibrate regularly if only to verify accuracy Labelling yourT C T1 orT2 will help ensure using the sameT...

Page 12: ...ain power supply terminals and secure amp clamp around the same line that the positive red test lead is connected to See Power Factor in top display and Power in bottom display Press SELECT to toggle Active Power W Reactive Power VAr Apparent Power VA and DC Power W CAUTION DO NOT MEASUREVOLTAGE LINES OR EXPOSETHE METERTO LIVE POWER LINES EXCEEDING 750VAC 1000VDC NOMINALVOLTAGE Power Watts VAr VA ...

Page 13: ... port and red test lead to theVΩ L2 L3 port on the SC680 You will see L1L2 blinking to indicate phase rotation test is ready to begin Step 2 Connect Leads Connect both black and red test leads to any two of the three phase voltage lines in question The line voltage will hold on the bottom display Blinking L1 and L2 disappear L3 will blink on top display to indicate test is ready for Step 2 Importa...

Page 14: ... Be sure voltage lines arewithin50 80Hztoperformthephaserotation test Modular Expandability Your SC680 is compatible with Fieldpiece Accessory Heads WithFieldpiece Accessory Heads youcanmeasureanyavailableparameter andread the measurement on your new meter s display in real time Hold Max and min Rotate the selector toVDC and stay in mV range Remove the probe tips of your test leads and connectyour...

Page 15: ...iece com for all Job Link System options Wireless Mode Send electrical measurements wirelessly from SC680 directly to the Job Link mobile app No JL2 transmitter required Sending Wireless Measurements 1 Select any switch position other than L1L2 and NCV on SC680 2 Press WIRELESS ON OFF button on meter 3 Favorite your SC680 by going to the measurement screen in the Job Link app 4 Tap on Electrical t...

Page 16: ...rement in Job Link mobile app SeeWireless Section for Job Link compatibility details HighVoltageWarning The symbol will display when measuring 30VAC VDC An audible beep will be heard and red LED will be shown Battery Replacement Whenyourmeter sbatteryislow thebatteryicon will appear empty and blink for 30 seconds bAtt will display and meter will power off Turn dial to OFF position disconnect test ...

Page 17: ...onment 32 F to 122 F 0 C to 50 C at 70 RH Storage temperature 4 F to 140 F 20 C to 60 C 0 to 80 RH with battery removed Accuracy Stated accuracy 73 F 9 F 23 C 5 C 75 RH Temperature coefficient 0 1 x specified accuracy per C 0 C to 19 C 32 F to 66 F 28 C to 50 C 82 F to 122 F APO Auto Power Off Approx 30 minutes Power Single standard 9 volt battery NEDA 1604 JIS 006P IEC 6F22 Battery life 100 hours...

Page 18: ...designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment...

Page 19: ...ective unit at its option subject to verification of the defect This warranty does not apply to defects resulting from abuse neglect accident unauthorized repair alteration or unreasonable use of the machine Any implied warranties arising from the sale of a Fieldpiece product including but not limited to implied warranties of merchantability and fitness for a particular purpose are limited to the ...

Page 20: ...38 SC680 Fieldpiece Instruments Inc 2019 v10 ...

Reviews: