background image

01

04

03

06            

02

05

      WARNINGS

Only use on TXV systems using 

either R410A or R22.

Ensure the system is powered 

OFF before installing the Charg-

ing Jacket. 

Severe injury can occur if the fan 

turns ON before hooks are se-

curely fastened towards the top 

of the condenser.

Wear eye protection.

Only use when the ambient dry 

bulb temperature is between 

37°F and 70°F (3°C to 21°C.)  

Using outside of this range can 

damage the air conditioner/heat 

pump.

Head pressure of the system 

needs to remain within the 

 

following safe ranges to avoid 

damage to the compressor or 

other equipment: 

    R22:   

55psig to 300psig 

    R410A:  97psig to 500psig

Stop the system if the head pres-

sure approaches these limits. 

Description

HVACR technicians typically 

cannot charge a cooling system in 

cold weather. The cold temperature 

removes too much heat from the 

condenser coils.

The Charging Jacket from Fieldpiece 

Instruments allow you to charge a TXV 

system when ambient temperatures 

are between 70°F and  37°F. 

It works by restricting the fan outlet 

of the condenser, in effect raising the 

temperature within the condsenser. 

This is a more effective method than 

blocking the incoming air to the 

condenser coil .

Look professional and increase  

your amount of possible jobs. No 

more trash bags or cardboard! Do it 

the right way.

Maintenance

Hand wash with cold water and 

mild detergent if needed and let air 

dry. Do not machine wash or dry. 

Fieldpiece

Charging Jacket

OPERATOR'S MANUAL

Model S365

How to Use

 

The Winter Charge Setup may 

only be used for equipment for which 

the air conditioning manufacturers 

approve the use of the Winter 

Charge Setup. Refer to (California’s) 

Energy Commissions website for 

the list of split system air condition 

units approved by the manufacturers 

to use the Winter Charge Setup. In 

addition to the requirements of this 

document, manufacturers may issue 

additional instructions/clarification 

for the equipment and procedures to 

be used to conduct the Winter Charge 

Setup. These additional instruction/

clarifications are also available on 

the (California) Energy Commission 

website. 

  

                   --  California Title 24 2013 Edition

Setup

1  Power down the system.

2  Install Charging Jacket:

   

 

 

 

 

 

 

 

A.  Tighten Bungie Cinch around top 

of condenser fan cage making sure 

not to block the airflow inlet (sides.) 

  B.  Fasten hooks securely so that the 

the fan does not eject the Charging 

Jacket when the system starts. 

  C.  Always start with the top open, 

then tighten the restriction string 

to restrict airflow as needed.

3  Make sure people and animals are 

clear of the condenser, then start 

the system.  

If using on a heat pump, 

set it to cooling mode.

4 Carefully adjust the restriction 

of the Charging Jacket until the 

difference

 between the high 

side and the low side pressures 

is between 160psi and 220psi 

(R410A) or 100psi and 145psi (R22). 

Restricting airflow increases the 

pressure difference.

Check Refrigerant Charge

5  Once the system is within the 

pressure difference range, allow 

the system to stabilize for 15 

minutes.

6 Calculate Actual Subcooling. 

(

T

condenser, saturation 

- T

 liquid line)

If your subcooling is more 

than three degrees less than the 

target subcooling, then you are 

undercharged.                    (continued)

!

!

!

!

!
!

!

!

!

!

!

BUNGIE CINCH

RESTRICTION STRING

Reviews: