background image

11

16

12

17

13

18

14

19

15

20

Calibrate an Adjustable Pressure  

  Switch

1. IMPORTANT: Be sure to use an adjustable 

pressure switch that will calibrate to the 

pressure rating of the pressure switch that 

is being changed out. Connect leads to the 

front jacks of the DRAFT SIMULATOR. Connect 

the leads to the normally open and common 

terminals on the pressure switch. It does not 

matter which lead goes to which terminal. 

2. Connect both hoses to the ports on the top 

of DRAFT SIMULATOR. Connect one hose to 

the negative side of the adjustable pressure 

switch and connect the other hose to the 

manometer. It does not matter which hose 

is connected to which port. 

3. IMPORTANT: Before starting the DRAFT 

SIMULATOR ensure the pressure dial is 

completely open by turning the dial 

counter-clockwise as far as it will go. 

Turn on and "zero" your manometer.  

Note the DRAFT SIMULATOR has two major 

speeds to accommodate different pressure 

switch ratings – a low speed and a high 

speed. The speeds are accessed alternately 

by pressing the switch multiple times:    

OFF – HIGH – OFF – LOW 

4. Turn on the DRAFT SIMULATOR. It is a good 

idea to start the DRAFT SIMULATOR in high 

speed to warm-up the motor for 10 seconds. 

5. Set the DRAFT SIMULATOR to the speed 

needed to calibrate the adjustable pres-

sure switch. Use low speed to calibrate an 

adjustable pressure switch rated between 

-0.10inWC and -1.50inWC. Use high speed to 

calibrate an adjustable pressure switch rated 

between 1.50inWC to 12.00inWC. 

6. IMPORTANT: An adjustable pressure switch 

must open at the desired pressure. Adjust the 

pressure dial on the DRAFT SIMULATOR until 

the desired pressure is reached as indicated 

on the manometer. 

If LED is OFF (switch is closed)– Slowly loosen the 

adjustment screw on the adjustable pressure 

switch until the LED light turns ON.

If LED is ON (switch is closed) – Slowly tighten 

the adjustment screw on the adjustable pres-

sure switch until the LED light turns OFF. The 

adjustable pressure switch is now calibrated 

within manufacturer’s specifications. 

Note: Pressures may slightly fluctuate during 

adjustments. You can fine tune an adjustable 

pressure switch by “closing the gap”. Slightly 

increase or decrease the pressure on the 

DRAFT SIMULATOR and tighten or loosen 

the adjustment screw on the switch until the 

switch is opening exactly at the desired rating. 

Note: When testing a "Dual Pressure Switch" 

it is only necessary to test the negative side 

as this switch only has one spring and one 

diaphragm similar to any negative pressure 

switch.

Test a Pressure Transducer

1. Connect one hose to the low side of the trans-

ducer the other hose to a manometer.

2. Connect a voltage meter to the transducer's 

terminals.

3. As you increase the vacuum, the voltage 

across the terminals will change based on 

the transducer's rating. Compare observed 

voltage to rated voltage to determine the 

health of the switch.

Specifications

Operating environment:

 32°F to 118°F (0°C to 48°C) at <80% RH

Storage temperature:

 -4°F to 140°F (-20°C to 60°C), 0 to 80% RH 

(with battery removed)

Power:

 4 x AA batteries

Battery life: 

approx 15 hours typical alkaline (7 hrs on high speed)

Maintenance

Clean the exterior with a dry cloth.  Do not 

use liquid.

Safety Information

The Pressure Switch is a safety device that 

prevents the furnace from running in an unsafe 

condition. An unsafe condition can result in 

injury, loss of property or even loss of life. 

1.  Before every use, check the DRAFT SIMULA-

TOR and the tubing for breaks or blockage. 

Check the tubing for any moisture as well. 

2.  Check for the presence of water in the pres-

sure switch before using the draft simulator. 

Do not use the draft simulator on a pressure 

switch that has water in it. Water can damage 

the DRAFT SIMULATOR and VOID the war-

ranty. Check the tubing for moisture build-up 

as well. 

3.  The DRAFT SIMULATOR is designed to pro-

duce a precise amount of negative pressure. 

Always use a manometer that is properly 

calibrated. Using a manometer that is out of 

calibration will give you incorrect readings. 

4.  Fieldpiece is not responsible for incorrect 

readings by faulty test equipment or un-

trained personnel. 

5.  In the interest of Safety, the DRAFT SIMULA-

TOR should only be used by trained, com-

petent professionals who understand the 

hazards and consider the risks of working on 

and with tools and equipment. 

6.  The pressure rating for the pressure switch is 

either stamped on the pressure switch or on 

a sticker attached to the pressure switch. Oth-

erwise, contact the vendor or manufacturer 

of the furnace to get that information. 

7.  Fieldpiece is not liable for any damages in-

curred by the misuse of the DRAFT SIMULA-

TOR. 

Note: Pressure switches have a rating of “(pres-

sure) WC PF”. This means that it is a (pressure) 

in inches of Water Column on Pressure Fall.  

Example: A -0.40 WC PF rating would mean 

that it should open at a negative 0.40 inches 

of water column. The pressure switch should 

close and more importantly “open” within 

10% of the manufacturer’s rating.

 

     

!

  WARNINGS  

!

Turn off power to furnace prior to testing 

to avoid low voltage shorting. 

If the pump stops while adjusting the 

pressure dial, immediately turn CCW to allow 

more airflow. The bleed port on the pressure 

switch may be blocked or you may need to 

use a different speed.

Limited Warranty

In the USA, this instrument is warranted 

against defects in material or workmanship for 

one year from date of purchase. Fieldpiece will 

replace or repair the defective unit, at its option, 

subject to verification of the defect.

This warranty does not apply to defects 

resulting from abuse, neglect, accident, 

unauthorized repair, alteration, or unreasonable 

use of the instrument.

Any implied warranties arising from the sale of 

a Fieldpiece product, including but not limited 

to implied warranties of merchantability and 

fitness for a particular purpose, are limited to 

the above. Fieldpiece shall not be liable for loss 

of use of the instrument or other incidental or 

consequential damages, expenses, or economic 

loss, or for any claim of such damage, expenses, 

or economic loss.

State laws vary. The above limitations or 

exclusions may not apply to you.

Obtaining Service

In the USA, call Fieldpiece Instruments for 

one-price-fix-all out of warranty service pricing. 

Send check or money order for the amount 

quoted. Send the meter freight prepaid to 

Fieldpiece Instruments. Send proof of date and 

location of purchase for in-warranty service. 

The meter will be repaired or replaced, at the 

option of Fieldpiece, and returned via least 

cost transportation. Outside of the USA, please 

visit www.fieldpiece.com for service contact 

information.

Reviews: