background image

01

06

02

07

03

08

04

09

05

10

Description

Correct pressure switch operation is integral 

to the safety of a furnace environment.

The DDSM1 teams with your accurate 

manometer to accurately test pressure switches. 

The DDSM1 creates a negative pressure 

(vacuum) and detects a closed switch. Your 

manometer tells you what the pressure is when 

the switch activates.

General Setup

   

Fieldpiece

Draft Simulator

OPERATOR'S 

MANUAL 

Model 

DDSM1

Controls and Ports

A

  Pressure dial (Clockwise increases vacuum.)

B

  Ports to negative side of switch and your 

manometer. (Close one OFF if only using one.)

C

  Power button:  

High Speed>OFF>Low Speed>OFF 

(some models use a rocker switch: I=Low, II=High)

D

 Closed-switch LED indicator.

E

  Jacks to switch terminals.

Functions

Test a Pressure Switch

WARNING: Turn off power to furnace prior to 

testing to avoid low voltage shorting. 

1.  Connect leads to normally open and com-

mon terminals of the pressure switch. It 

does not matter which lead goes to which 

terminal. 

2.  Connect both hoses to the ports on the top of 

DRAFT SIMULATOR. Connect one hose to the 

negative side of the pressure switch and  the 

other to your manometer. It does not matter 

which hose is connected to the manometer 

and the pressure switch. 

3. IMPORTANT: Before starting the DRAFT 

SIMULATOR, ensure the pressure dial 

is completely open by turning the dial 

counter-clockwise as far as it will go. 

Turn on and "zero" your manometer.  

There are two major speeds to accommo-

date different pressure switch ratings – a 

low speed and a high speed. The speeds are 

accessed alternately by pressing the power 

button multiple times as shown below:  

OFF – HIGH – OFF – LOW 

4. Turn on the DRAFT SIMULATOR. It is a good 

idea to start the DRAFT SIMULATOR in high 

speed to warm-up the motor for 10 seconds. 

5.  Set the DRAFT SIMULATOR to the major speed 

needed for testing the pressure switch. Use 

low speed to test pressure switches rated 

between -0.10 inches of water column and 

-1.50inWC. Use high speed to test pressure 

switches rated 1.50inWC  to 12.00inWC. 

6. Slowly close the pressure dial by turning it 

clockwise (increasing the vacuum) paying 

attention to the indicator light on the front 

of the DRAFT SIMULATOR and the readings 

on the manometer.

7. The light will come on when the pressure 

switch closes. Note the reading on the ma-

nometer. Manufacturers have a rating when 

the pressure switch should close. A good 

pressure switch will close within 10% of the 

manufacturer’s rating.

8. To see when the switch opens, slowly open 

the pressure dial by turning it CCW. When the 

light of the DRAFT SIMULATOR goes off, note 

the reading of the manometer. The reading 

should be within 10% of the rating on the 

pressure switch.

NOTE: Most pressure switches have bleed ports 

in them to drain moisture. This also helps to 

avoid excess pressure created by the draft 

inducer and controls the amount of pressure 

required to close the switch. The amount 

of pressure required to close and open the 

switch should still be within 10% of the 

manufacturer’s rating. The pressure required 

to close the switch should never exceed the 

amount of pressure created by the draft 

inducer.

NOTE: Many pressure switches have an orifice 

in the port. This increases the time it takes to 

close or open the pressure switch. This does 

not mean it takes more or less pressure to 

close the pressure switch. The pressure switch 

should still close and open within 10% of the 

rating. 

NOTE:  Dual-port manometers are usually setup 

to use the positive port (P1) with the DRAFT 

SIMULATOR.

Indications of a Pressure Switch out of 

calibration, weak or bad diaphragm or a bad 

micro switch in the pressure switch:

o The pressure switch will not close or open 

within 10% of its rating. 

o  The indicator light on the DRAFT SIMULATOR 

“flickers” on and off rapidly. 

o Manometer readings fluctuate when no ad-

justments are made to the pressure dial on 

the DRAFT SIMULATOR. 

o  The measured readings are greatly affected 

when the hose to the pressure switch is 

pinched.

Pinch Test - Proving the  

  Diaphragm

o  Test the pressure switch and note the findings 

using the DRAFT SIMULATOR. 

o  Pinch the hose closed to the pressure switch 

while performing the test. 

o  If the pressures differ more than 20% from 

the original findings, you may have a bad, 

cracked, or leaking diaphragm in the pressure 

switch. If the pressure doesn’t differ you may 

have a blocked bleed port. 

Prove or Rule Out the Inducer

o If the pressure created by the inducer mea-

sures more than enough to close the pressure 

switch but the DRAFT SIMULATOR proves 

the pressure switch to be good, the inducer 

may not be providing enough cfm (cubic feet 

per minute) to close the switch. The inducer 

should be replaced. 

A

B

C

E

E

D

inWC

One hose goes to manometer.

One hose goes to 

negative side of switch.

Leads go to switch terminals.

(normally open and common)

 

99 Washington Street 
Melrose, MA 02176 

Phone

 781-665-

1400

Toll Free 1-800-517-8431

 

Visit us at www.T

estEquipmentDepot.com

Reviews: