WARNING:

 

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage 

or blindness.Never operate the UV-Aire

 Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

Page 7 of 12

P/N 46648100  09/18  Rev J

REPLACEMENT PROCEDURE (LAMP ONLY)

WARNING:

WARNING:

    Disconnect power to the transfomer 

    Disconnect power to the transfomer or unplug the  

or unplug the  

   

      

   

      120V power 

120V power cord 

cord before starting replacement 

before starting replacement 

       

      procedure

       

      procedure.

NOTE:   Wear disposable, non-absorbent protective gloves prior to 
       replacement procedure in case of accidental breakage of 
      glass.

1. Rotate the Duo or UV-Aire ballast assembly counter-clockwise 

until it stops. (See Figure 9)

2. Remove the ballast assembly and lamp from the mounting base. 

(See Figure 10)

3. Remove the lamp from the lamp socket.
4. Install the replacement lamp into lamp socket. Do not handle the 

lamp with bare hands. Oils on the hands tend to reduce lamp 
intensity.

5. Wipe off the glass with the supplied alcohol wipe.

6. Position the ballast assembly power cord 90° to the viewport 

hole on the mounting base. (See Figure 10)

7. Slide the lamp through the hole in the mounting base.

8. Press the ballast against the mounting base. Rotate the ballast 

assembly clockwise until it stops and is locked in place. (See 
Figure 11)

9.  After assembly is fi rmly in place, reconnect power to transformer 

or ballast.  Check lamp operation by looking through the viewport 
hole. A blue glow should be seen in the duct.

10. After replacing the lamp, make sure to install the Lamp 

Replacement Label. Print the date on the label and apply to the 
side of ballast assembly.

Figure 9  (Removal)

Figure 10

MAINTENANCE

WARNING:  Disconnect power to the transformer before commencing 

WARNING:  Disconnect power to the transformer before commencing inspection and cleaning.

inspection and cleaning.

NOTE:  Wear disposable, non-absorbent protective gloves prior to inspection procedure in case of accidental 

    

    breakage of glass.

1. We recommend inspecting and cleaning the lamp at least every 6 months. Frequency depends upon the 

environment. Such as: the type of air fi lter, duration of use and replacement cycle.

2. To maintain maximum output intensity, replace the UV-Aire lamp annually. The lamp should operate 

continuously for maximum lamp life and light effectiveness.

3. 

Do not attempt to clean the catalytic honeycomb core with cleaning solutions. The catalyst is radiated with 
short wave ultraviolet light during period of non-air fl ow and is self-cleaning. If there is build up blocking 
the catalytic cells, sit the unit on end, on a fl at surface, with electrical enclosure facing up. Use low-pressure, 
compressed air to blow the surface of the catalytic cells free of blockage.

Summary of Contents for Healthy Home System DUO-11/120

Page 1: ...nstallation The PCUV 16UA provides a new mounting structure with photo catalytic VOC reduction and carbon absorption technology for the existing lamp installation This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or condition nor for use in the mitigation treatment or prevention of any disease or condition READ THESE INSTRUCTIONS CAREFULLY AND COMP...

Page 2: ...of hand oils causes a reduction in the light intensity WARNING Before installing or servicing a humidifier air filter HVAC system or this unit etc always WARNING Before installing or servicing a humidifier air filter HVAC system or this unit etc always turn all power OFF and have unit unplugged Electrical shock can cause personal injury or death Never turn all power OFF and have unit unplugged Ele...

Page 3: ...ing Duo installation instructions for guidance on installation location required clearances and safety precautions etc clearances and safety precautions etc c c If the PCUV 16UA may NOT be installed in the existing location If the PCUV 16UA may NOT be installed in the existing location cover cover and seal the existing and seal the existingmounting mounting location cutout with approprate material...

Page 4: ...ly installed standard 120V electrical outlet with 15 amp circuit protection Do not connect to extension cords or extend or remove the plug from the power cord Make sure the Duo power cord is protected from damage and inspect the cord for damage or defect Do not use the Duo 120V unit if the power cord is damaged or defective d The Duo unit may be installed on either the supply or return plenum e Th...

Page 5: ... the sight glass may be seen above the center hole in the mounting base in Figure 3 There is a pair of holes in the Duo mounting flange that allow the sight glass in the base to align with in either position f Insert the UVC lamp pins into the ballast socket see Figure 4 Note The lamp has one long pin that must be aligned with the recessed terminal in the ballast socket Do NOT directly touch the b...

Page 6: ...E USED TO PROVIDE POWER TO THE DUO 24V UNIT TO THE DUO 24V UNIT 4 For 24V models connect the ballast power cord to the provided 24V transformer terminals using the included crimp on fork terminals P N 46648100 09 18 Rev J Figure 5 Figure 6 5 For 24V models restore power to the circuit providing power to the 24V transformer 6 For 120V models plug the power cord into the 120V electrical outlet 7 Loo...

Page 7: ...tate the ballast assembly clockwise until it stops and is locked in place See Figure 11 9 After assembly is firmly in place reconnect power to transformer or ballast Check lamp operation by looking through the viewport hole A blue glow should be seen in the duct 10 After replacing the lamp make sure to install the Lamp Replacement Label Print the date on the label and apply to the side of ballast ...

Page 8: ...tain a small amount of mercury like a typical fluorescent lamp Check with your local waste management authority for local disposal or recycling requirements According to the EPA s Universal Waste Rule these types of lamps may be disposed of into household waste WARNING WARNING Never touch broken lamp or internal contents of lamp Never touch broken lamp or internal contents of lamp The lamp contain...

Page 9: ...b and carbon media can be slid out of the opening in the back of the unit see Figure 13 The honeycomb panel and the carbon media insert must be removed together even if only one needs replacing 6 Replace any removed pieces of either Pro Cell honeycomb or carbon media with the specified replacement parts only When sliding the replacement pieces back into the unit check and make sure the Pro Cell ho...

Page 10: ...warranty For proper operation 24V models requires 24VAC at all times 2 Check to make sure 24VAC power is available at the transformer or 120V at the electrical outlet 3 If lamp does not light up pull back metal washer on mounting base If lamp comes on the base needs tightening to ensure that the safety switch is fully engaged 4 If lamp does not light up remove the ballast from the base and re inst...

Page 11: ...ner bag and the disposable gloves in a sealed garbage bag 4 Check with your local waste management authority for local disposal or recycling requirements According to the EPA s Universal Waste Rule these types of lamps may be disposed of into household waste 5 Wash hands and remove and wash clothes for added safety measures Replacement Part Number 46649301 11 Lamp Assy Duo 46649302 14 Lamp Assy Du...

Page 12: ...ite www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or any Field Controls product visit www fieldcontrols com www fieldcontrols com Field Controls Technical Support Field Controls Technical Support 1 800 742 8368 1 800 742 8368 fieldtec fieldcontrols com fieldtec fieldcontrols com Field Controls LLC...