OPERATION: 

The GSK-160A is a normally closed single-pole, single throw (SPST) 
thermally-activated switch that is intended to be wired in series with the 
burner control safety circuit of an 80+ efficiency-rated, fan-assisted, gas-
fired appliance.  When subjected to temperatures above approximately 
160°F, the switch will open, interrupting the safety circuit, thereby 
preventing the burner from firing. When allowed to cool, the switch will 
automatically reset, allowing the burner to fire. Activation of the GSK switch 
may cause burner lockout on some appliances. 

INSTALLATION ON DRAFT CONTROLS: 

NOTE:

  GSK style switches are designed for mounting on draft control 

models 4” MG1 through 9” MG1. Larger size draft controls required the FTS 
series switches. 

U

NIT WITH 

MG1 D

RAFT 

C

ONTROL SUPPLIED WITH 

GSK 

IN A KIT

1.  Mount the switch onto the threaded stud on the top front of the 

MG1, using the supplied 8-32 locking nut.  

2.  Swing the gate in and out to verify smooth operation through the range of 

operation. 

U

NIT WITH 

D

RAFT 

C

ONTROL SUPPLIED SEPARATELY

1.  Mount the switch with the supplied #5-40 machine screw and nut on the top 

front of the MG1. (Note, the head of the screw is to be on the inside of the 
ring. (See Figure 2)  

2.  Swing the gate in and out to verify smooth operation through the range of 

operation. 

INSTALLATION LOCATION:

 

For single-appliance venting applications, install the draft control with GSK-160A 
directly above the appliance as shown in Figure 3, unless otherwise instructed by the 
appliance manufacturer.  For co-venting applications with an atmospheric-burner-equipped appliance (such as a water 
heater), install the draft control with GSK-160A immediately below the tee or wye fitting, as shown by the dashed lines in 
the figure, to help prevent spillage at the water heater.  A Field Controls Barohood

TM

 with one GSK-3 mounted 

(recommended) or two GSK-3 spill switches mounted on the draft hood (available in kit SSK-1), wired into the 
thermocouple circuit (use one TCA-1 for either method) is recommended for additional safety. 