Field Controls DUO-11/24V Manual Download Page 6

page 6

WARNING:

 

Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage 

or blindness.Never operate the UV-Aire

 Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

REPLACEMENT PROCEDURE
WARNING: Disconnect power to the transfomer before starting replacement 
procedure.
NOTE:   Wear disposable, non-absorbent protective gloves prior to 
replacement  
procedure in case of accidental breakage of glass.

1.  Rotate the UV-Aire ballast assembly counter-clockwise until it stops. 

(See Figure 6)

2.  Remove the ballast assembly and lamp from the mounting base. (See 

Figure 7)

3.  Remove the lamp from the lamp socket.

4.  Install the replacement lamp into lamp socket. Do not handle the lamp 

with bare hands. Oils on the hands tend to reduce lamp intensity.

5. Wipe off  the glass with the supplied alcohol wipe.

6.  Position the ballast assembly power cord 90° to the viewport hole on the 

mounting base. (See Figure 6)

7.  Slide the lamp through the hole in the mounting base.

8.  Press the ballast against the mounting base. Rotate the ballast assembly 

clockwise until it stops and is locked in place. (See Figure 8)

9.  After assembly is fi rmly in place, reconnect power to transformer.  Check lamp 

operation by looking through the viewport hole. A blue glow should be seen in the 
duct.

10.  After replacing the lamp, make sure to install the Lamp Replacement Label. Print the 

date on the label and apply to the side of ballast assembly.

NOTE: If blue light leaks through any portion of plenum and/or around mounting plate, 
unplug power supply cord immediately and seal aff ected areas and/or rotate ballast 
and repeat step #8.

11.  UV lamps contain a small amount of mercury, like a typical fl uorescent lamp. Check with your local waste 

management authority for local disposal or recyclingrequirements. According to the EPA's Universal Waste 
Rule, these types of lamps may be disposed of into household waste.

WARNING: Never touch broken lamp or internal contents of lamp. The lamp contains mercury.

NOTE: In case of accidental exposure to internal contents of lamp, wash hands and any other aff ected skin area 
with mild detergent. Remove aff ected clothing immediately. If skin surface is pierced, seek medical attention 
immediately.

Figure 6  (Removal)

Figure 7

Figure 8 (Installed)

Summary of Contents for DUO-11/24V

Page 1: ... 11 24V DUO 14 24V PCUV 16UA The Duo 24V models produce germicidal UVC Band light rays which sterilize and reduce airborne microorganisms and reduce Volatile Organic Compounds VOC s by a photocatalytic chemical reaction as air passes through a heating or air conditioning system It is installed in the main supply or return duct and operates continuously to automatically purify the air in the home 2...

Page 2: ...do not touch lamp or other contents in carton Close carton and return to seller immediately In case of accidental exposure to internal contents of lamp wash hands and any other affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately NOTE If you touch the glass of the lamp you should wipe the glass clean with isopropy...

Page 3: ...ctboard when installed using the included Ductboard Adapter Plate see Figure 1 2 Install the Duo 24V unit a Hold or temporarily tape the included Ductboard Adapter Plate in the location chosen for installation and using the plate as a template mark the mounting surface using the outermost slots in the plate see Figure 1 Alternatively a 5 3 8 square may be marked on the mounting surface b Cut out t...

Page 4: ...a downward air flow direction note that the round sight glass hole will be upstream of the ballast when properly installed f Insert the UVC lamp pins into the ballast socket see Figure 3 Note the lamp has one long pin that must be aligned with the recessed terminal in the ballast socket D o NOT directly touch the bulb lamp glass section with bare hands Wear oil free cotton type gloves when han dli...

Page 5: ... annually The lamp should operate continuously for maximum lamp life and light effectiveness 3 Ensure that power has been disconnected to the circuit that will provide power to the 24V transformer and install the transformer as directed in the installation instructions included with the transformer WARNING MAKE SURE POWER IS DISCONNECTED TO THE CIRCUIT TO BE USED TO PROVIDE POWER TO THE DUO 24V UN...

Page 6: ... ballast against the mounting base Rotate the ballast assembly clockwise until it stops and is locked in place See Figure 8 9 After assembly is firmly in place reconnect power to transformer Check lamp operation by looking through the viewport hole A blue glow should be seen in the duct 10 After replacing the lamp make sure to install the Lamp Replacement Label Print the date on the label and appl...

Page 7: ...ngaged 4 If lamp does not light up remove the ballast from the base and re install it onto the base ensuring that the finger projecting from the base engages into the safety switch slot in the ballast Repeat step 3 5 If lamp does not light up after performing Steps 3 and 4 replace lamp REPLACEMENT PARTS LIST For replacement parts contact Field Controls at Phone 252 522 3031 Fax 252 522 0214 Email ...

Page 8: ...46648100 06 15 The health aspects associated with the use of these products and their ability to aid in disinfecting of environmental air have not been investigated by UL Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com warranty ...