INTERNAL WIRING FOR CK-CONTROL KIT: DIAGRAM A & B

L1 to 1 on timer

T2 to timer relay base

M to 3 on timer

T3 to N/O on pressure switch

T1 to common on pressure switch

Timer base to common on pressure switch

Diagram B

P/N 46285300 Rev F 01/18

WIRING 750mV GAS VALVE SYSTEM WITH ELECTRONIC TEMPERATURE CONTROL

CAUTION: Disconnect electrical power when wiring power venter.

When  wiring  with  a  power-pile  system  having  an  intergrated  electronic  control,  which  have  a
diagnostic  LED  indicator;  please  refer  to  Diagram  C,  on  page  7.    You  will  not  use  the  TCA  thermocouple 
adapter, supplied with the CK-91FV.  Install the GSK spill switches per instruction and connect to the red wire 
and the thermal door switch per diagram. Wire the venter motor and controls in accordance with the National
Electrical  Code,  manufacturer’s  recommendations  and/or  applicable  local  codes.  Units  must  be
grounded. Check ground circuit to make certain that the unit has been properly grounded.  The wiring should be
protected by an overcurrent circuit device rated at 15 amperes.

 CAUTION must be taken to ensure that the

wiring does not come into contact with any heat source.

  All line voltage and safety control circuits between the 

venter and the appliance must be wired in accordance with the National Electrical Code for class one wiring or 
equivalent methods.  Route the venter motor and control wiring with an appropriate wiring method.

Summary of Contents for CK-91FV

Page 1: ...D COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION Installation Date Installed By Phone 24 VAC SYSTEM CONTROL KIT Designed for use with the SWG Series Power Venter for controlling Natural Gas or L P...

Page 2: ...asten the flexible conduit from the SWG Venter into the conduit connector Mount the CK 91FV junction box or installer supplied junction box onto the wall or floor joist without straining the flexible...

Page 3: ...TION DO NOT use the supplied collar when mounting draft control to Type B Vent Pipe Install by using a Type B Vent Pipe Tee 1 Install a vent pipe reducer or increaser into the inner pipe and fasten us...

Page 4: ...properly adjust the pressure switch as specified above could lead to improper operation of the pressure switch which will result in a hazardous condition and bodily harm THERMOSTAT HEAT ANTICIPATOR A...

Page 5: ...ignition module or gas valve if standing pilot which would normally be 24 volts hot on a call for heat With spark ignition systems this terminal could be TH W 24 V THS or T1 depending on the spark ig...

Page 6: ...Install the GSK spill switches per instruction and connect to the red wire and the thermal door switch per diagram Wire the venter motor and controls in accordance with the National Electrical Code ma...

Page 7: ...couple circuit halting the gas flow to the pilot and burner 3 Wait 2 to 3 minutes Reset the spillage switches and light the pilot then perform a second safety spillage test Steps 1 and 2 CAUTION If fo...

Page 8: ...Pressure Switch 46284200 GSK 3 Spillage Switch 46086400 Post Purge Timer 46282800 Pressure Switch 46083000 TCA 1 Thermocouple Adaptor 46082700 REPAIR AND REPLACEMENT PARTS TROUBLE SHOOTING HINTS 1 Ven...

Reviews: