ADJUSTMENTS
PRESSURE SWITCH ADJUSTMENTS

With the venter air fl ow set and the appliance operating 
at the best operating effi

  ciency, adjust the pressure 

switch by rotating the adjustment screw clockwise until 
the burner shuts off , then rotate the adjustment screw 
counterclockwise until the burner fi res. Rotate the 
adjustment screw an additional 

1

4

 turn counterclockwise 

to ensure proper switch setting. 
(See Figure 6)

POST PURGE TIMING ADJUSTMENT

To adjust the post purge time, refer to 
Figures 7 & 8.

For timer that looks like Figure 7: Rotate the timer 
adjustment on the timer clockwise to increase the 
operation time. To decrease the operation time, 
rotate the timer adjustment counterclockwise.

For timer that looks like Figure 8: Rotate the 
timer adjustment on the timer counterclockwise 
to increase the operation time. To decrease 
the operation time, rotate the timer adjustment 
clockwise.

*Typical post purge time should be between 3 to 
5 min.

Figure 6

Figure 7

Figure 8

Summary of Contents for CK-61

Page 1: ...uch work familiar with all the precautions required and has complied with all the requirements of the authority having jurisdiction READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING W...

Page 2: ...on box mount the flexible conduit connector onto a 2 x 4 installer supplied junction box 2 Fasten the flexible conduit from the SWG Venter into the conduit connector Mount the CK 61 junction box or in...

Page 3: ...t circuit device rated at 15 amperes Caution must be taken to ensure that the wiring does not come into contact with any heat source All line voltage and safety control circuits between the venter and...

Page 4: ...page 4 Diagram D Riello Burner Application Diagram C Typical Wiring for Oil Fired WarmAir Furnace with a Honeywell ST9103 Control Board...

Page 5: ...page 5 Diagram E Multiple Oil Fired Systems...

Page 6: ...e proper switch setting See Figure 6 POST PURGE TIMING ADJUSTMENT To adjust the post purge time refer to Figures 7 8 For timer that looks like Figure 7 Rotate the timer adjustment on the timer clockwi...

Page 7: ...ts d Thermostat is satisfied relay is de energized burner stops and post purge timer operates venter motor for approximately 3 to 5 minutes 2 While system is operating disconnect power to the venter m...

Page 8: ...hone 252 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46144900 Rev L 04 16 WARRANTY For warranty about this or any Field Controls product visit www fieldcontrols com warranty...

Reviews: