Diagram B
WIRING 750mV GAS VALVE SYSTEM WITH ELECTRONIC TEMPERATURE CONTROL
CAUTION: Disconnect electrical power when wiring power venter.
When wiring with a power-pile system having an intergrated electronic control, which have a
diagnostic LED indicator; please refer to Diagram B. You will not use the TCA thermocouple adapter,
supplied with the CK-20FV. Install the GSK spill switches per instruction and connect to the red wire and the
thermal door switch per diagram. Wire the venter motor and controls in accordance with the National
Electrical Code, manufacturer’s recommendations and/or applicable local codes. Units must be
grounded. Check ground circuit to make certain that the unit has been properly grounded. The wiring should
be protected by an overcurrent circuit device rated at 15 amperes.
CAUTION must be taken to ensure that
the wiring does not come into contact with any heat source.
All line voltage and safety control circuits between
the venter and the appliance must be wired in accordance with the National Electrical Code for class one
wiring or equivalent methods. Route the venter motor and control wiring with an appropriate wiring method.