Page 9
Chart A
VI.
BULB MOUNTING BRACKET SELECTION
The UV-AIRE
TM
units come with an angled mounting bracket and flat mounting bracket to position the bulb either
straight or at an angle. Choose one or the other bracket method best suited for your needs. Refer to the
configurations chart below when making your selection.
A
NGLED
L
AMP
M
OUNTING
B
RACKET
S
PECIFICATIONS
Use the specifications below to determine allowable clearances for proper mounting of the UV-Aire™ unit on the duct.
LAMP OFFSET DIMENSIONS
Unit
Min Duct
Size
(inches)
A
B
UV-12C
9x12
8-1/2
6-1/2
UV-18C
14x18
13-1/2
10-5/16
UV-28C
22X24
21-3/8
16-1/4
UV-28
22X24
21-3/8
16-1/4
UV-12HP
9x12
8-1/2
6-1/2
UV-18HP
14x18
13-1/2
10-5/16
UV-28HP
22X24
21-3/8
16-1/4
UV-12HPC
9x12
8-1/2
6-1/2
UV-18HPC
14x18
13-1/2
10-5/16
UV-28HPC
22X24
21-3/8
16-1/4
Standard 90°
Installation
(Flat Bracket)
(16” Duct)
Patent Pending
Angled Installation
Single Lamp
(Angled Bracket)
(16” Duct)
UV-Aire™ Configurations
Chart B
Good
Best
WARNING:
Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or
blindness.
Never operate the UV-Aire™ Air Purifying System out of the plenum
. Avoid touching the glass portion of the lamp with your
hands.
Exclusive 5 Position Mounting
Straight
Angled Positions