Field Controls 46382500 Manual Download Page 4

 

Page 4

S

YSTEM 

C

ONTROL 

C

HECK 

O

UT 

P

ROCEDURES

1.  Adjust the thermostat to call for heat and observe the power venting system for proper operation 

sequence. (Repeat if necessary) 

a.  Thermostat calls for heat. 

b.  Relay is energized and venter motor starts. 

c.  Pressure switch closes and burner starts. 

d.  Thermostat is satisfied, the burner stops. 

2.  While system is operating, disconnect power to the venter motor. This should open the pressure 

switch contacts and stop burner operation. 

TROUBLE SHOOTING HINTS 

1.  Venter does not activate when thermostat calls for heat: 

a.  Check wiring. 

b.  Check gas pressure switch for continuity across terminals when gas valve is pressurized. 

c.  Check gas pressure. 

2.  Flue gas odor: 

a.  Check system draft. 

b.  Check for negative pressure in building. 

 

 

DO NOT DESTROY 

T

HESE 

I

NSTRUCTIONS 

M

UST 

R

EMAIN 

W

ITH 

E

QUIPMENT

 

Installation Information 

 

Model No.: ________________________________________  

Installer’s Name: ___________________________________  

Installer’s Company: ________________________________  

Phone No.: _______________________________________  

Date of Installation: _________________________________  

P/N 46382500 05/00 