Superdoctor
1.
Logon to SuperMicroDoctor utility,
username: admin
password: admin
In an 8 bay server fans 4,5,6, A & B should not be selected. There should be no voltages selected for CPU2.
V DIMM EFand GH should not be selected. The temperature for CPU2 should not be selected.
In a 16 bay server fans 4, A & B should not be selected. There should be no voltages selected for CPU2. V
DIMM EF and GH should not be selected. The temperature for CPU2 should not be selected.
In a 2 CPU configuration the Voltage for CPU2, memory slots V DIMM EF and GH and temperature for CPU2
should all be selected.
2.
Test fan failure is detected. Remove one fan from the fan tray. Fan speed should increase on the
remaining fans. An alarm should sound and a red indicator on the front of the server should
indicate
fan failure. Reinsert the fan to it’s position. The
fan should spin up and all fans should
return to normal operating speed and the alarm should be silenced. The LED on the front should be
turned off.
3.
(all fans working properly)