5 Wires and Cables
5.2.1
External Power Cable
Function
The external power cables, including the -48 V power cable, 0 V power cable, and
protection earth ground cable, are used to induct the power source in the equipment
room to the PDP inside the cabinet.
Model
Table 5-1 describes the model numbers of the external power cables.
Table 5-1
Model Numbers of the External Power Cables
PDP Model
Cable Type
Cable Model
Note
Cable Color
PDP850A
(3000064)
-48 V power cable
3696097-X (16 mm
2
)
408000003-X (25 mm
2
)
Blue
0 V power cable
408000033-X (16 mm
2
)
408000006-X (25 mm
2
)
Black
Protection earth
ground cable
3696100-X (16 mm
2
)
408000019-X (25 mm
2
)
Yellow- / green
u
X
indicates the cable length, which is determined by the distance for cable connection in the project.
u
The 16 mm
2
power cable is used by default.
u
When the cable connection distance between the head of row cabinet and the PDP is within 25 m, the 16 mm
2
power cable should be used.
u
When the cable connection distance between the head of row cabinet and the PDP is between 25 m and 40 m,
the 25 mm
2
power cable should be used.
u
The 16 mm
2
and 25 mm
2
cables should not be used together.
u
Generally, two blue cables, two black cables and one yellow- / green cable are used as a set of cables by default.
If two subracks are mounted in a cabinet, use four blue cables, four black cables, and one yellow- / green cable
as a set of cables.
Structure
Cable Model
Description
Illustration
408000019/408000006
Uninsulated ring te
bare wire
3696097/408000003/3696100
Cord end te bare wire
408000033
Copper cord end te
bare wire
Version: A
53