If the optical loss is less than 5dB, connect the two ends of the optical cable to the APU and use the 
tuning software to disable both processors. When configured in this manner, the APU will not alarm 
when the fiber is shaken. The alarm relay will change states if the fiber is broken, cut, or unplugged. If 
the IP port is being used, the processor will output a fault indicator via XML messaging when the cable 
is disconnected or cut. Figure 3 below displays a screenshot from the FD322 Tuning Software 
reflecting the proper parameters for cable break detector applications; observe that all the detection 
related settings are disabled.  
 
 
 

Figure 3 

 

 

The cut and climb  settings  are  disabled,  so  movement  of  the  cable  does  not  cause  an  alarm;  only 
cuts, breaks, or unplugging the connector will cause an alarm with these settings.  

 

 

 