HEATING REQUEST
As the contact of room thermostat closes, if the mainboard is in winter mode, the system
pump is
only
activated
if the temperature of the primary heat exchanger is higher than the
temperature set by parameter N°6.
If the value of temperature measured by the primary heat exchanger probe is lower than the
programmed delivery setpoint, the triac are ignited in sequence as per the required power.
This occurs only after a settable time by parameter N°5.
The instant power of the boiler and the related control of triac G1-G4 takes place by
means of PID regulator.
MEANING OF THE KEYS OF TEMPERATURE MENU
To log in temperature menu, press simultaneously J3 and J5 keys. The symbol
F
F
F
F
will
appear on the display.
KEY
FUNCTION
J7
Exit by temperature menu
J2
Temperature index increase
J3
Temperature index decrease
MEANING OF KEYS OF PARAMETERS MENU
To log in parameters menu, press simultaneously the keys J2 and J6 for 4 seconds.
The symbol
F
F
F
F
will appear on the display.
KEY
FUNCTION
J5
Parameter value decrease
J6
Parameter value increase
J7
Exit by parameters menu
J2
Parameter index increase
J3
Parameter index decrease